Fonderie SIME RX 26 BF Скачать руководство пользователя страница 6

2.9

POSITIONING OF OUTLET

TERMINALS

The  outlet  terminals  for  forced  draught

systems  may  be  located  on  the  outer

walls of the building. 

Table  2

shows  approximate,  non-binding

minimum  distances  to  be  met  for  a  buil-

ding of the type shown in fig. 6. 

41

max 0,5 m

max 0,5 m

C12

C52

C32

C42

C82

min. 700

Fig. 5

LIST OF ACCESSORIES THAT ALLOW THE 
CONFIGURATIONS  INDICATED  ARE  SUPPLIED
ON REQUEST: 

– Separate flue kit code 8089905
– 90° elbow MF code 8077404
– 90° insulated elbow MF code 8077408
– Extension L. 1000 code 8077303
– Insulated extension L. 1000 code 8077306
– Outlet terminal code 8089501
– Int.-est. ring kit code 8091500
– Inlet terminal code 8089500
– 45° elbow MF code 8077406
– Condensation outlet L. 135 code 8092800
– Doubler fitting code 8091400
– Tile with articulated joint code 8091300
– Roof outlet terminal L. 1390 code 8091201
– Tee condensation outlet code 8093300

WARNING: 
The outlet and intake ducts of type C52 cannot
be located on opposite walls.

TABLE 2

Siting of terminal

Appliances from 7 to 35 kW

(distances in mm)

A - below openable window

600

B - below ventilation opening

600

C - below eaves

300

D - below balcony (1)

300

E - from adjacent window

400

F - from adjacent ventilation opening

600

G - from horizontal or vertical soil or drain pipes (2)

300

H - from corner of building

300

I - from recess in building

300

L - from ground level or other treadable surface

2500

M - between two terminals set vertically

1500

N - between two terminals set horizontally

1000

O - from a surface facing without 

openings or terminals

2000

P - as above but with openings and terminals

3000

1) Terminals below a practicable balcony must be located in such a way that the total path of the smoke from its outlet point from the terminal to its outlet

point from the external perimeter of the balcony, including the height of possible railings, is not less than 2000 mm.(?)

2)  When siting terminals, where materials that may be subject to the action of the combustion products are present in the vicinity, e.g., eaves, gutters and

downspouts painted or made of plastic material, projecting timberwork, etc., distances of not less than 1500 mm must be adopted, unless adequate shiel-

ding is provided to guard these materials.

Fig. 6

Содержание RX 26 BF

Страница 1: ...ype of gas supplied Check that the flue pipe for the outlet of the products of the combustion is unobstructed and or has been properly installed Make sure that any shutoff valves are open Make sure th...

Страница 2: ...BF Heat output min nom kW 23 2 31 0 kcal h 19 950 26 660 Heat input min nom kW 26 2 34 0 kcal h 22 530 29 240 Cast iron sections n 4 Water content l 15 Power consumption W 155 Maximum water head bar...

Страница 3: ...ty valve goes into action When sizing gas piping from the meter to the boiler take into account both the volume flow rates consumption in m3 h and the relative density of the gas in question The secti...

Страница 4: ...The boiler is supplied with the connections required for coaxial ducts that can be turned in any direction The maximum horizontal length of the duct must not exceed 2 8 meters Maximum two extensions c...

Страница 5: ...alculation in that the sum of the head losses of the single fittings is less than 6 00 mm H2O Intake Outlet 6 meter horizontal pipe 80 x 0 20 1 20 6 meter horizontal pipe 80 x 0 40 2 40 n 2 90 elbows...

Страница 6: ...o 35 kW distances in mm A below openable window 600 B below ventilation opening 600 C below eaves 300 D below balcony 1 300 E from adjacent window 400 F from adjacent ventilation opening 600 G from ho...

Страница 7: ...nected to an efficient eathing system SIME cannot be held liable for damage to people or things that is due to non earthing of the boiler Always turn off the power supply before doing any work on the...

Страница 8: ...continuos spark ing even if the burner is on After 10 sec onds the sparking stops and so does the burner while the lock out lamp appears to be on It occurs if the phase and neutral position on the te...

Страница 9: ...ating pressure values have been changed After have ultimated the conversion of the boiler please stick onto the casing panel the plate showing the relevant feeding gas which is included into the kit N...

Страница 10: ...operation The fan works but with less revolutions and therefore it does not enable the flue gas pressure switch replace it The principal burner does not burn prop erly flame too high yellow flame Mak...

Страница 11: ...e if it is lower than 1 bar When the operation is over close the fill up cock GAS CONVERSION If the gas that is to be used if different than the one that the boiler has been prearran ged for contact a...

Отзывы: