pipe insulator, with a density of 50 kg/m

3

.

The maximum overall length of the intake

and  exhaust  ducts  depends  on  the  head

losses  of  the  single  fittings  installed  and

must not exceed than 6,00 mm H

2

O. 

During  installation  use  only  original  SIME

accessories  and  make  sure  that  the  con-

nection is carried out properly, as indicated

in the accessory instructions.

For  head  losses  in  the  fittings,  refer  to

Table 1

.

2.8.1

Separate flue kit 

(fig. 4)

The  required  intake  diaphragm  is  supplied

with  the  separate  duct  kit  code  8089905,

according  to  the  maximum  load  allowed  in

both ducts, as indicated in fig. 4/a.

2.8.2

Outlet systems

The  diagrams  in  fig.  5  illustrate  a  number

of  examples  of  different  types  of  separate

outlets.

40

Fig. 4/a

5

7

6

2

4

3

1

Fig. 4

Example  of  allowable  installation  calculation  in  that  the  sum  of  the  head  losses  of  the

single fittings is less than 6,00 mm H

2

O:

Intake 

Outlet

6 meter horizontal pipe ø 80 x 0,20

1,20

6 meter horizontal pipe ø 80 x 0,40

2,40

n° 2 90° elbows ø 80 x 0,30

0,60

n° 2 90° elbows ø 80 x 0,50

1,00

n° 1 terminal ø 80

0,10

0,40

Total head loss

1,90

+

3,80   =

5,7 mm H

2

O

The intake diaphragm is to be removed with this maximum loss of load.

TABLE 1

Accessories ø 80

Load loss (mm H

2

O)

Intake

Outlet

Roof out. Intake

90° elbow MF

0,30

0,50

45° elbow MF

0,20

0,40

Extension L. 1000 (horizontal)

0,20

0,40

Extension L. 1000 (vertical)

0,30

0,30

Outlet terminal

0,40

Intake terminal

0,10

Manifold

0,30

Roof outlet terminal  L. 1390

0,60

Tee condensation outlet

1,10

KEY
1

Blank flange 

2  Outlet flange
3  Screw
4  Sponge sheath ø 125/95
5  Intake collar
6  Intake diaphragm
7  Sponge sheath ø 100/78

N° diaphragm sectors to remove

Total load loss

mm H

2

O

Pa

1

0 ÷ 1

0  ÷

9,8

3

1 ÷ 2

9,8  ÷ 19,6

4

2 ÷ 3

19,6  ÷ 29,4

6

3 ÷ 4

29,4  ÷ 39,2

Remove the diaphragm

4 ÷ 6

39,2  ÷ 58,8

DIAPHRAGM SECTOR

Содержание RX 26 BF

Страница 1: ...ype of gas supplied Check that the flue pipe for the outlet of the products of the combustion is unobstructed and or has been properly installed Make sure that any shutoff valves are open Make sure th...

Страница 2: ...BF Heat output min nom kW 23 2 31 0 kcal h 19 950 26 660 Heat input min nom kW 26 2 34 0 kcal h 22 530 29 240 Cast iron sections n 4 Water content l 15 Power consumption W 155 Maximum water head bar...

Страница 3: ...ty valve goes into action When sizing gas piping from the meter to the boiler take into account both the volume flow rates consumption in m3 h and the relative density of the gas in question The secti...

Страница 4: ...The boiler is supplied with the connections required for coaxial ducts that can be turned in any direction The maximum horizontal length of the duct must not exceed 2 8 meters Maximum two extensions c...

Страница 5: ...alculation in that the sum of the head losses of the single fittings is less than 6 00 mm H2O Intake Outlet 6 meter horizontal pipe 80 x 0 20 1 20 6 meter horizontal pipe 80 x 0 40 2 40 n 2 90 elbows...

Страница 6: ...o 35 kW distances in mm A below openable window 600 B below ventilation opening 600 C below eaves 300 D below balcony 1 300 E from adjacent window 400 F from adjacent ventilation opening 600 G from ho...

Страница 7: ...nected to an efficient eathing system SIME cannot be held liable for damage to people or things that is due to non earthing of the boiler Always turn off the power supply before doing any work on the...

Страница 8: ...continuos spark ing even if the burner is on After 10 sec onds the sparking stops and so does the burner while the lock out lamp appears to be on It occurs if the phase and neutral position on the te...

Страница 9: ...ating pressure values have been changed After have ultimated the conversion of the boiler please stick onto the casing panel the plate showing the relevant feeding gas which is included into the kit N...

Страница 10: ...operation The fan works but with less revolutions and therefore it does not enable the flue gas pressure switch replace it The principal burner does not burn prop erly flame too high yellow flame Mak...

Страница 11: ...e if it is lower than 1 bar When the operation is over close the fill up cock GAS CONVERSION If the gas that is to be used if different than the one that the boiler has been prearran ged for contact a...

Отзывы: