background image

Problem

1. Icemaker will not run.

System status:
compressor, gearmotor,
and fan motor inoperative.

2. Compressor will not run.

System status: gearmotor
and fan motor run.

3. Unit cycles intermittently.

System status:
compressor, gearmotor,
and fan motor cycle.

4. Low ice production.

Poor quality ice.

Indicators/possible cause

1. No power to unit.
2. Open bin level control.
3. Water OK LED (WTR) not on.

4. 20M or 2ND LED is on indicating that first

or second torque error has occurred.

5. Gearmotor locked up (immediate torque

error indicated by LEDs when board is
reset).

6. Centrifugal switch stuck in open or closed

position (immediate torque error indicated
by LEDs when board is reset).

1. Condenser coil plugged causing

overheating.

2. Defective starting capacitor.
3. Defective starting relay.
4. Open motor winding.
5. No power output from compressor output

terminal on control board.

1. Hi temp cut out open (W/C units only)

due to high head pressure.

2. Float reservoir running dry, sensing

probe signalling for system to shut down.

1. Dirty condenser coil.
2. Restricted air flow to condenser coil.
3. Mineral coated evaporator.
4. High ambient water supply and/or air

temperature.

5. Improper exhaust air provisions.
6. Faulty expansion valve.
7. Low refrigerant charge.
8. Superheat incorrect.
9. Inefficient compressor.

Corrective action

1. Check that unit is plugged in, circuit

breakers are on.

2. Adjust or replace ice level control.
3. Check reservoir for water, restore

water to unit.

4. See Problem #6 below.
5. Repair or replace gearmotor.
6. Replace centrifugal switch.

1. Clean condenser coil and replace

overload if necessary.

2. Replace start capacitor.
3. Replace relay.
4. Ohm out windings and replace

compressor if necessary. 

5. Check terminal connection and

replace control board if necessary.

1a. Check supply and temperature of

water to condenser.

1b. Check discharge pressure and

adjust water regulating valve.

1c. Clean condenser coil.

2. Check water supply to float and

float operation. Part #207588 will
have flashing WTR LED.

1. Clean condenser.
2. Remove obstruction.
3. Clean evaporator.
4. Precool water and/or install air duct

per Follett installation manual.

5. Provide proper exhaust air

provisions per Follett installation
manual.

6. Replace expansion valve.
7. Check for leaks; repair, evacuate,

and weigh in correct charge.

8. Check that TEV sensing bulb is

securely clamped in place and not
damaged; check that insulated bulb
cover is in place.

9. Replace compressor.

Troubleshooting chart

• Flashing water LED at any time indicates that water signal to board has been lost for more than one second.
• Ten-second delay: There is a 10 second delay in reaction to loss of water (WTR) or bin (B-E) signals. If signals 

are not lost for more than 10 seconds, no reaction will occur.

13

Содержание D5A

Страница 1: ...654R01 UL R5A icemaker with countertop dispenser T5A W icemaker mounted on ice storage bin R5A icemakers with undercounter dispenser 801 Church Lane PO Box D Easton PA 18044 Toll free 800 523 9361 888...

Страница 2: ...ator information Cleaning procedures Recommended monthly cleaning of condenser air cooled icemaker only 1 Use vacuum cleaner or stiff brush to carefully clean condenser coils of air cooled icemaker to...

Страница 3: ...from ice storage area and allow ice made during the sanitizing process to fall into ice bin area Note If bin will not be cleaned at this time place a large pan in bin storage area to catch ice or conn...

Страница 4: ...ce the icemaker Operational and diagnostic sequences The wiring diagrams which follow illustrate the circuitry of Follett icemakers used with ice dispensers Both normal operation of the icemaker stage...

Страница 5: ...in by the initial high current draw of the compressor The B E and WTR LED remain on M GRD L1 L1 L2 L2 L2 L2 L2 COMPRESSOR FAN DRIVE DR C 20M 60M 2ND WTR B T B E RESET X GRD G B W FAN BLACK WHITE BLACK...

Страница 6: ...ntinues to run for 60 seconds The purpose of this function is to drive the remaining ice out of the evaporator and to boil off any refrigerant remaining in the evaporator M GRD L1 L1 L2 L2 L2 L2 L2 CO...

Страница 7: ...AN DRIVE DR C 20M 60M 2ND WTR B T B E RESET X GRD G B W FAN BLACK WHITE BLACK BLACK R ORANGE S S L COMPRESSOR C RED BLACK BLACK WHITE INPUT POWER CONTROL BOARD BLACK GEARMOTOR 24V COMMON LINE VAC RED...

Страница 8: ...dition If the icemaker runs without problems for 60 minutes and no additional torque errors occur the 60M LED will go off M GRD L1 L1 L2 L2 L2 L2 L2 COMPRESSOR FAN DRIVE DR C 20M 60M 2ND WTR B T B E R...

Страница 9: ...L1 L2 WATER SENSOR PWR 8 Diagnostic sequence Stage 10 If the water level in the float reservoir drops to an unacceptable level the WTR LED will go out shutting the icemaker off Also the BT LED will c...

Страница 10: ...GRD G B W FAN BLACK WHITE BLACK BLACK R ORANGE S S L COMPRESSOR C RED BLACK BLACK WHITE INPUT POWER CONTROL BOARD BLACK GEARMOTOR 24V COMMON LINE VAC RED RED COMPRESSOR SWITCH WHITE BLACK BIN T STAT W...

Страница 11: ...1 C 80 F 26 7 C 90 F 32 2 C 100 F 37 8 C 6 3A 6 5A 6 7A 6 9A 7 1A Water cooled Water temp at float 50 F 10 C 60 F 15 6 C 70 F 21 1 C 80 F 26 7 C 90 F 32 2 C 6 6A 6 7A 6 7A 6 8A 6 9A Locked rotor amps...

Страница 12: ...his period the system should not rise above 1000 microns If the system rises above 1000 microns evacuate the system again If the system rises above 1000 microns for a second time check the system for...

Страница 13: ...ting base 4 Fill gearmotor shaft well with food grade grease 5 Install condensate shield and seat against gearmotor boss 6 Install bearing O ring in groove in evaporator mounting base 7 Lower bottom b...

Страница 14: ...efficient compressor Corrective action 1 Check that unit is plugged in circuit breakers are on 2 Adjust or replace ice level control 3 Check reservoir for water restore water to unit 4 See Problem 6 b...

Страница 15: ...dirty condenser coil 2 Compressor not pumping 3 Low refrigerant charge 1 Compressor switch in OFF position 2 No output on compressor and fan motor terminals on control board 1 Replace O ring 1 Elimin...

Страница 16: ...Air cooled icemaker right side Air cooled icemaker left side 15 1 2 3 4 5 6 7 11 10 12 8 9 12 6 5 16 17 15 14 13 2 18...

Страница 17: ...3 Tubing plastic 5 8 ID x 13 16 OD sold by foot 9 501190 Mounting bracket gearbox 10 501992 Gearbox motor assembly 115V 60Hz 11 501993 Gearbox motor assembly 230V 50Hz 11 501191 Tubing plastic food gr...

Страница 18: ...Water cooled icemaker right side Water cooled icemaker left side 17 1 3 4 5 6 7 8 12 11 9 13 10 13 2 14 18 16 15 17 19 20...

Страница 19: ...rmal 8 501289 Drain pan evaporator 9 500623 Tubing plastic 5 8 ID x 13 16 OD sold by foot 10 501992 Gearbox motor assembly 115V 60Hz 11 501993 Gearbox motor assembly 230V 50Hz 11 501190 Mounting brack...

Страница 20: ...e Not shown 501992 Gearbox motor assembly 13 501993 Gearbox motor assbly 230V 13 501190 Mounting base gearbox Not shown 502220 Compression nozzle with double drain below 502221 Compression nozzle with...

Страница 21: ...97 Bearing needle 2 required 17 500781 2 Gear 3 pinion assembly 18 500798 Shaft 2 gear 19 500878 4 Gear 5 pinion assembly 20 501989 Gearcase 21 501994 Vent plug 23 501991 Bearing ball sealed 24 501144...

Страница 22: ...50Hz 2 502331 Board control circuit 115V 60Hz 3 502349 Board control circuit 230V 50Hz 3 502116 Water sensor 4 500006 Switch on off compressor 5 500514 Bin thermostat T5A W icemakers only Not shown 50...

Страница 23: ...transport tube insulation 501176 Ice tube insulation sold by the foot Ice tube end kit Required length of transport tube 500366 must be ordered Tube insulation 501176 must also be ordered for all rem...

Страница 24: ...Enamel All U150 series with air cooled icemakers R5A None Enamel All U150 series with water cooled icemakers R5W None Enamel All U300 series with air cooled icemakers R5A None Enamel All U300 series...

Отзывы: