background image

SENTINEL II 5700

 

3

Bank  of  foggers  controlled  by  turning  supply 

pump on and off, under timer control. 

Pressurized liquid source, such as the house water 

supply, feeding a zone of foggers.  Solenoid valve 

is controlled by repeat cycle timer.

Fog  heads  controlled  individually  by  solenoid 

valves in supply lines. Chemicals can be injected 

“in-line”  with  a  proportioning  injector.  Valves 

controlled by multiple timers. 

INSTALLATION PLANNING

A Sentinel II installation can contain any number of fog heads, all supplied 

with liquid from a central source. This can be located wherever convenient. 

If fogging chemicals must be diluted, you can use a mixing reservoir or inject 

them in-line with a proportional mixer. Low pressure tubing or other low cost 

material is used to connect heads to the liquid source.
Heads can be operated individually or connected together in zones. Nozzles 

can be rotated to any discharge angle. A metering valve on each head (open 

counterclockwise  for  more  flow,  larger  droplets)  is  used  to  set  fog  proper-

ties.
Power  requirements,  piping  sizes  and  valving  are  determined  by  the  head 

layout and expected liquid flows. Each head draws 10A at 120VAC (5A at 

240V). A head’s effective range (in still air) is 75-100 ft for small droplets, and 

30-60 ft for larger ones. Liquid output is 4-10 oz/min for small droplets, and 

10-20 oz/min for large.

System Control

When the inlet pressure at the fog head exceeds 3 psi, the pressure switch 

turns on the head and generates fog. To control an individual head, feed it 

separately. To  control  several  heads  at  once,  connect  them  to  a  common 

liquid line.
Many installations use repeat cycle timers to activate solenoid valves or low 

pressure transfer pumps (see examples below).

Legend:

Содержание Sentinel II 5700

Страница 1: ...Read all instructions carefully before starting the installation Save this manual for future use OWNER S MANUAL EXTREME DUTY REMOTE CONTROL DUAL HEAD FOGGING SYSTEM Sentinel II 5700...

Страница 2: ...feed inlet it turns on the blower and opens a solenoid valve allowing liquid to flow through a metering valve and into the nozzle The Sentinel II 5700 head lets you adjust fog droplet size At the fine...

Страница 3: ...connect heads to the liquid source Heads can be operated individually or connected together in zones Nozzles can be rotated to any discharge angle A metering valve on each head open counterclockwise f...

Страница 4: ...placed where they are needed and spaced for uniform coverage To move a head or add a new one just mount it where needed plug into an electric outlet and attach a liquid feed line 2 Droplet Size We re...

Страница 5: ...LIST Item Part Number No Description 120 Volt 240 Volt 1 a Pressure Switch 3 psi 520 520 2 Metering Valve 530 530 3 a Relay 540 545 4 Motor Brushes pair 550 555 5 Blower 560 565 6 a Solenoid Valve 57...

Страница 6: ...ion Tighten all band clamps Insert gray liquid connector into side of box 3 Test operation Make sure POWER switch is OFF and CONTROL switch is set to PRESSURE Plug unit into a 15A grounded receptacle...

Страница 7: ...g Replace the retaining bracket and the two screws 7 Replace cooling fan housing If you break the retaining clips you can purchase a different type of retaining clip from Fogmaster TROUBLESHOOTING CHA...

Страница 8: ...parties or subjected to any but the specified voltage This warranty is limited to the original purchaser only and does not include claims for incidental or consequential damages resulting from the no...

Отзывы: