Focal Point MUSE P23 Скачать руководство пользователя страница 5

VENTILATION (continued)

Any ventilation fitted must comply with BS 5871 part 4 and BS 5440 part 2. Ventilation fitted under, or within imme-
diate vicinity of the appliance must not be used as it may adversely effect performance of the ODS system.The appli-
ance MUST NOT be installed in a bedroom, bathroom or any sleeping area. For Republic of Ireland, see relevant
rules in force. The appliance should not be installed within 1 metre of any air vent.

UNPACKING THE APPLIANCE

Remove the outer packaging, remove any instructions or fixing kits.

Read ALL these instructions before continuing to unpack or install this appliance.

If the decorative frame is supplied attached to the firebox, remove the frame by removal of the lower two securing
thumbscrews on either side of the firebox, and then unhook the frame from the top two thumbscrews.

Lift off the remaining packaging components and remove the contents of the box.

Check that the components supplied correlate with the component checklist. Please dispose of all the packaging
materials at your local recycling centre.

COMPONENT CHECKLIST

QUANTITY

DESCRIPTION

1

Firebox and burner assembly

Set of manufacturers instructions

1

Decorative frame assembly

1

Screw and wall plug pack

1

Rubber grommet

1

Fitting template

GAS SUPPLY ROUTES 

There are four possible entry points for the gas supply
pipework to enter the appliance firebox. These entry
points are ‘knock out’ type holes.

Non-concealed gas connections may be made using
the entry points at either end of the firebox or the
one in the bottom of the firebox.A concealed gas con-
nection may be made using the knock out hole in the
centre back of the firebox. Select the most appropriate
entry point and knock out the relevant hole 
No more than 1.5m of 8mm diameter pipe must be
used to avoid unnecessary pressure drops.

If a concealed gas connection is to be made, the supply pipe should always be sleeved through walls and floors using
the shortest possible route.

For concealed supply pipe routing, pipes must (where possible) be vertical and providing there is sufficient wall thick-
ness available, they should be placed in pipe chases. Horizontal pipe runs should be avoided. Prior to chasing a solid
wall, an inspection should be made to note the proximity of any cables/sockets outlets which may already be buried.

Pipes must be secured using suitable clips and protected against corrosion. Ideally factory finished protected
pipework and fittings should be used. Joints should be kept to a minimum and compression fittings must not be used.
The pipework installation must be tested for tightness before any protection is applied and/or the pipework and fit-
tings are buried.

4

5.0

5.1

6.0

4.1

©

2007 Focal Point Fires plc.

Содержание MUSE P23

Страница 1: ...FIRE Focal Point Fires plc Christchurch Dorset BH23 2BT Tel 01202 499330 Fax 01202 499326 www focalpointfires co uk e mail sales focalpointfires co uk It is the LAW that all gas appliances and fitting...

Страница 2: ...be installed in a correctly sized room see section 3 1 and the correct purpose provided ventilation must be pro vided see section 4 1 It should be noted that heaters create warm air currents These cur...

Страница 3: ...nt spaces but these spaces must not be separated by a door To calculate a room size in cubic metres m3 divide the room volume in cubic feet ft3 by 35 3 SITE REQUIREMENTS This appliance is designed to...

Страница 4: ...liance The appliance is designed to be wall mounted alone and not in conjunction with any type of combustible fire surround No combustible shelves should be positioned on the wall above the appliance...

Страница 5: ...late GAS SUPPLY ROUTES There are four possible entry points for the gas supply pipework to enter the appliance firebox These entry points are knock out type holes Non concealed gas connections may be...

Страница 6: ...alignment of the appliance with a spirit level as small adjustments can still be made if necessary When this has been checked tighten all four fixing screws fully To access the upper fixing screws in...

Страница 7: ...ircumstances the piezo electric spark fails the pilot cannot be lit manually SETTING PRESSURE The pressure test point is located on the left hand side of the appliance on the main burner pipe next to...

Страница 8: ...e from the gas supply Ensure that the fire is fully cold before attempting service A suggested proce dure for servicing is detailed below 1 Lay out the dustsheet and tools 2 Remove the decorative fram...

Страница 9: ...can be removed from the base of the pilot unit using two spanners to make cleaning easier Do not damage or try to dismantle the pilot injector The unit is factory set and the only check necessary is...

Страница 10: ...r obstruction Faulty thermocouple replace pilot unit Blocked pilot clean out Blocked lint gauze clean Hold control knob in for longer Check control knob does not foul indicator plate If the pilot will...

Страница 11: ...ALL MOUNTED FLUELESS GAS FIRE Next Retail Ltd Desford Road Enderby Leicester LE19 4AT Helpline Telephone 0844 844 8999 It is the LAW that all gas appliances and fittings are installed by a competent p...

Страница 12: ...ombustion monitoring system ODS DO NOT burn any foreign material on this fire Under no circumstances shall the appliance be used if the glass front door or panel has been removed damaged or is open DO...

Страница 13: ...ce It should be established that any mirrors or picture frames etc to be positioned on the wall above the appliance are able to withstand prolonged exposure to moderate heat and moisture before procee...

Страница 14: ...m and removal of the draught should resolve this The appliance can then be re lit in accordance with the previous section If pilot disturbance is not the cause then the ODS safety system may be in ope...

Отзывы: