Operating manual EMGZ300
8
6
Installation and wiring
Caution
Proper function of the Tension Measuring Amplifier is only guaranteed with the recommended
application of the components. In case of other arrangement, heavy malfunction can be the
result. Therefore, the installation instructions on the following pages must be followed strictly.
Caution
Local installation regulations are to preserve safety of electric equipment. They are not taken
into consideration by this operating manual. However, they have to be followed strictly.
6.1
Mounting and wiring of the electronic unit
The insert card support block can be mounted in a control cabinet. Wiring to the terminals is
done according to wiring diagram (fig. 4). The electronic card then will be inserted into the
insert block. It will be locked by a stop hook (fig. 3).
Caution
Improper handling may damage the fragile electronic equipment! Don’t use rough tools as
screwdrivers or pliers! Touch earthed metal part to discharge static electricity before touching
the electronic unit!
6.2
Mounting the force sensors
Mounting of the force sensors is done referring to the FMS Installation manual which is
delivered together with the force sensors.
Wiring to the terminals of the electronic unit is done according to wiring diagram (fig. 4).
Notice
Connecting the shield of the signal cable to the electronic unit
and
to the force sensor may
cause ground circuits which may interfere the measuring signal massively. Malfunction can be
the result. The shield should be connected only to the electronic unit. On the „force sensor
side“, the shield should stay open.