Operating Manual EMGZ611A...614A
17
8.2
Configuring the Electronic Unit
Prior to the first calibration, the following settings must be done for each channel
(ref. to „9. Parametrization“):
Global parameters
Language
Required display language
Measuring system
Metric (default) or US standard
Channel parameters
Force of sensor
Ref. to nameplate of the force sensor
Unit of sensor
Ref. to nameplate of the force sensor
Sensitivity
FMS force sensors = 1.8mV/V (default)
1 or 2 sensors
1 or 2 per channel
Scale output
Which tension feedback refers to 10V resp.
20mA?
Config. output
0-10V and 0...20mA (default)
or 0-10V and 4...20mA
or -10V...+10V
Notice: With a tension signal 0...10V, tension
and current output are active at the same time.
Jumpers for the analog outputs (ref. also to „14. Technical Reference“)
Channels 1 / 2 / 3 / 4
0...10V (Default) or ±10V,
corresponding to parameter Config. output
Note
Wrong setting of the parameters may cause malfunction of the electronic unit!
Setting of the parameters must be done carefully prior to setting into operation!