VENTING INSTALLATION
Continued
Note: Vertical (V
1
) + Vertical (V
2
) = 40' max.
Figure 23 - Vertical Venting
Configuration Using Two 90° Elbows
(Vertical Round High Wind Termination
Shown)
45° Elbow
Vertical Venting
V = 40' max.
Figure 24 - Vertical Venting
Configuration With No Horizontal Run
(Vertical Round High Wind Termination
Shown)
45° Elbow
HIGH ALTITUDE INSTALLATION
Your FMI PRODUCTS, LLC direct-vent
fireplace has been tested and approved for
elevations.
When installing this fireplace at an elevation
above 2000 feet, you may need to decrease
the input rating by changing the existing
burner orifice to a smaller size. Reduce input
4% for each 1000 feet above sea level. Check
with your local gas company for proper orifice
size identification.
Consult your local gas company to help deter
-
mine the proper orifice for your location.
For assistance with any high altitude installa
-
tion contact FMI PRODUCTS, LLC’s Customer
Service Department at 1-866-328-4537.
Note: Install
restrictor into inner
collar of fireplace
as shown.
Venting with Two 90° Elbows
Vertical (V
1
) Horizontal (H)
5' min.
6' max.
6' min.
12' max.
7' min.
18' max.
8' min.
20' max.
Note: Install restrictor
into inner collar of
fireplace as shown.