www.fmiproducts.com
116236-01M
15
INSTALLATION FOR VERTICAL
TERMINATION
Note: Vertical restrictor must be installed in
all vertical installations.
1. Determine route your vertical venting
will take. If ceiling joists, roof rafters or
other framing will obstruct venting system,
consider an offset (see Figure 19) to avoid
cutting load bearing members.
Note: Pay
special attention to these installation
instructions for required clearances (air
space) to combustibles when passing
through ceilings, walls, roofs, enclosures,
attic rafters, etc. Do not pack air spaces
with insulation. Also note maximum
vertical rise of venting system and any
maximum horizontal offset limitations.
2. Set fireplace in desired location. Drop a
plumb line down from ceiling to position
of fireplace exit flue. Mark center point
where vent will penetrate ceiling. Drill a
small locating hole at this point.
Drop a plumb line from inside of roof to
locating hole in ceiling. Mark center point
where vent will penetrate roof. Drill a small
locating hole at this point.
Flat Ceiling Installation
1. Cut a 11
1
/
2
" square hole in ceiling using
locating hole as a center point. Open
-
ing should be framed to 11
1
/
2
" x 11
1
/
2
"
(29.2 cm x 29.2 cm) inside dimensions, as
shown in Figure 9 on page 10 using fram
-
ing lumber the same size as ceiling joists.
If area above ceiling is an insulated ceiling
or and attic space, nail firestop from top
side. This prevents loose insulation from
falling into required clearance space. If
area above ceiling is a living space, in
-
stall firestop below framed hole. Firestop
should be installed with no less than three
nails per side (see Figure 20).
2. Assemble the desired lengths of pipe and
elbows necessary to reach from fireplace
flue up through firestop. Be sure all pipe
and elbow connections are fully twist-
locked (see Figure 8, page 10).
3. Cut a hole in roof using locating hole as
a center point. (Cover any exposed open
vent pipes before cutting hole in roof.) The
11
1
/
2
" x 11
1
/
2
" hole must be measured
on the horizontal; actual length may be
larger depending on pitch of roof. There
must be a 1" clearance from vent pipe to
combustible materials. Frame opening as
shown in Figure 9, page 10.
4. Connect a section of pipe and extend up
through hole.
Note: If an offset is needed to avoid
obstructions, you must support vent pipe
every 3 feet. Use wall straps for this pur-
pose (see Figure 19). Whenever possible,
use 45° elbows instead of 90° elbows. A
45° elbow offers less restriction to the flow
of flue gases and intake air.
VENTING INSTALLATION
Continued
Figure 19 - Offset with Wall Strap and 45°
Elbows
45° Elbow
Wall Strap
Roof
Flashing
Ceiling Firestop
Figure 20 - Installing Firestop
If area above is a living space, install
firestop below framed hole.
If area above is an attic or insulated area,
install firestop above framed hole.