FMI Masonry MM39 Скачать руководство пользователя страница 8

7

  For conventional framing, where the floor joists are parallel 

with the sides of the firebox, the addition of floor joists to align 

with  the  anchor  brackets  allows  the  brackets  to  be  directly 

connected to the floor joists. 

 

  Note that additional floor joists may be required to support 

the weight of the firebox and chimney. Where the floor joists run 

parallel to the front of the firebox, anchorage can be accomplished 

in like manner as shown in Figure 5 using blocking between the 

floor joist.

  For floors supported by I-Joists, the method of anchorage is 

illustrated in Figures 6 and 7. Figure 10 illustrates the general 

arrangement of anchorage to floor framing.

  It is important to take into consideration that the load for the 

Grand  Meridian  Fireplace  must  be  considered  as  additional 

dead load that will have to be supported by the floor framing. 

Additional floor joists or I-joists may be required as determined 

by the licensed design professional.

  The dead weights for the fireplace are noted in Table I. It is 

the task and responsibility of the general contractor/installer to 

see that the proper reinforcement for weight loads are made by 

a licensed design professional prior to the fireplace installation.

  As stated above, it is desirable to place additional framing 

for alignment of anchor rods. Refer to Figure 10 for anchor rod 

locations.

Figure 5

Floor Sheathing 

not shown for 

clarity

Anchor Bracket

Assembly

EXAMPLE ONLY

2X FLOOR JOIST

2X FLOOR JOIST

A35 Brackets 

(16 required)

I-Jo

ist

Simpson 

Strong-Tie 

A-35 or 

equivalent

Figure 6

I-Joist Anchoring 

Top View

Example Only

I-JOISTS

Anchor 

Brackets

Figure 7

I-Joist 

Anchoring 

Bottom 

View

Example Only

Содержание Masonry MM39

Страница 1: ...and approved by PFS under ANSI Z21 91 for use with any ANSI Z21 11 2 approved gas logs FORUSEONLYWITHALISTEDGAS FIREDUNVENTED DECORATIVE ROOM HEATER NOT TO EXCEED 40 000 BTU HR DO NOT BUILD A WOOD FI...

Страница 2: ...WITH ANSI Z21 91 2007 VENTLESS FIREBOX ENCLOSURES FOR GAS FIRED UNVENTED DECORATIVE ROOM HEATERS FOR USE WITH LISTED ANSI Z21 11 2 UNVENTED DECORATIVE ROOM HEATERS NOT TO EXCEED 40 000 BTU HR 0 10 NO...

Страница 3: ...d Diagram 5 9 12 2 7 1 3A 2X 2X 3X 7X 2X 8X 3 6 11 Warning Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may re...

Страница 4: ...ireplace Parts List ITEM P N DESCRIPTION QTY 1 MFP39 1 MFP44 1 MFP49 1 HEARTH Left or Right 2 2 MFP39 2 MFP44 2 MFP49 2 REAR WALL 4 3 MFP39 3 MFP44 3 MFP49 3 SIDE WALL 7 3A MFP39 3A MFP44 3A MFP49 3A...

Страница 5: ...erve as a primary heat source rather the fireplace was expressly created as a supplemental source of heat The Grand Meridian Fireplace is Designed for Use Only with any Vent free decorative gas log se...

Страница 6: ...ace if not enough fresh air is available See Air for Combustion and Ventilation page 8 If the fireplace keeps shutting off see appliance manufacturers troubleshooting instructions 9 Do not run firepla...

Страница 7: ...ian fireplace Check with the local jurisdiction before you get started Supporting Floor Systems Floor Framing It is important to take into consideration that the load for the Grand Meridian Fireplace...

Страница 8: ...dian Fireplace must be considered as additional dead load that will have to be supported by the floor framing Additional floor joists or I joists may be required as determined by the licensed design p...

Страница 9: ...d structural members having a moisture content of less than 16 per cent at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for th...

Страница 10: ...designed to be custom finished with facing trim and mantle to be an owner option However all such trim material must meet standard fireplace code requirements Non combustible facing material must be...

Страница 11: ...he house to operate You must provide adequate fresh air for these appliances This will insure proper venting of vented fuel burning appliances Non combustible Flex Hose Figure 16 Exterior Providing Ad...

Страница 12: ..._ Btu hr Total _ _______ Btu hr Example Gas water heater 40 000 Btu hr Vent free fireplace 36 000 Btu hr Total 76 000 Btu hr Do not include direct vented gas appliances Direct vent draws combustion ai...

Страница 13: ...prior to assembly This will minimize shrinkage and cracks developing in the joint areas Best way to accomplish this is with a bucket of water and a large sponge Dip sponge into water and apply a liber...

Страница 14: ...28 Apply mortar between joints 12 inch rebar Mix a batch of mortar and prepare Right Side Hearth bottom 2 surface to be bonded as shown in Figure 18 Figure 18 1 2 AWAY FROM EDGES 1 2 MORTAR BEAD TYPIC...

Страница 15: ...rebar to all 8 cells as shown in Figure 22 The rebar should enter the holes in the Hearth and lie adjacent to the 12 rebar secured in subfloor Then fill cells with approx 2 cu ft Ready Mix Concrete F...

Страница 16: ...Fuel Gas Code ANSI Z223 1 This gas pipe provision must only be connected to an approved vent free gas log heater certified to ANSI Z21 11 2 heater standard Check local building codes for specific pip...

Страница 17: ...smells created from the heater and fireplace curing We suggest operating the heater for several 30 minute intervals allowing the fireplace to cool for an hour in between This will allow any moisture i...

Страница 18: ...ncrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MI...

Страница 19: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Страница 20: ...components FMI PRODUCTS LLC is not responsible for misuse or mishandling of component parts Nothing in this warranty makes FMI PRODUCTS LLC or any entity thereof liable in any respect for any injury...

Отзывы: