www.fmiproducts.com
115254-01C
9
wall connecting the two spaces (see options
1 and 2, Figure 3). You can also remove door
into adjoining room (see option 3, Figure 3).
Follow the
National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation
for required size of ventilation
grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two perma
-
AIR FOR COMbUSTION AND VENTILATION
Continued
Figure 4 - Ventilation Air from Outdoors
Figure 3 - Ventilation Air from Inside
Building
nent openings: one within 12" of the ceiling
and one within 12" of the floor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the
National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section
5.3, Air for Combustion and Ventilation
for
required size of ventilation grills or ducts.
IMPORTANT:
Do not provide openings for
inlet or outlet air into attic if attic has a thermo
-
stat-controlled power vent. Heated air entering
the attic will activate the power vent.
INSTALLATION
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills
Into
Adjoining
Room,
Option 1
12"
12"
Outlet
Air
Ventilated
Attic
Outlet
Air
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
CAUTION: Log heaters
installed in this firebox create
warm air currents. These cur-
rents move heat to wall surfaces
next to firebox. Installing firebox
next to vinyl or cloth wall cover-
ings or operating firebox where
impurities (such as, but not
limited to, tobacco smoke, aro-
matic candles, cleaning fluids,
oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.
IMPORTANT:
Vent-free gas log heaters add
moisture to the air. Although this is beneficial,
installing firebox in rooms without enough
ventilation air may cause mildew to form from
too much moisture. See
Air for Combustion
and Ventilation
, page 7.
WARNING: A qualified ser-
vice person must install firebox.
Follow all local codes.
WARNING: Never install the
firebox
• in a bedroom or bathroom*
• in a recreational vehicle
• where curtains, furniture,
clothing or other flammable
objects are less than 42" from
the front, top or sides of the
firebox
• in high traffic areas
• in windy or drafty areas
* Unless the installed log set is
rated at 10,000 Btu/Hr or less.