background image

www.fmiproducts.com

125326-01A

6

The space in the example is a confined space 

because the actual Btu/Hr used is more than the 

maximum  Btu/Hr  the  space  can  support. You 

must provide additional fresh air. Your options 

are as follows:
A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides an 

unconfined space, remove door to adjoining 

room or add ventilation grills between rooms. 

See 

Ventilation Air From Inside Building

.

B.  Vent  room  directly  to  the  outdoors.  See 

Ventilation Air From Outdoors

, page 7.

C.  Install a lower Btu/Hr heater, if lower Btu/Hr 

size makes room unconfined. 

If the actual Btu/Hr used is less than the maxi

-

mum Btu/Hr the space can support,

 

the space is 

an unconfined space. You will need no additional 

fresh air ventilation.

 WARNING: If the area in which 

the heater may be operated does 

not meet the required volume for 

indoor combustion air, combus-

tion and ventilation air shall be 

provided by one of the methods 

described in the 

National Fuel 

Gas Code, ANSI Z223.1/NFPA 54, 

the

 International Fuel Gas Code,

 

or applicable local codes.

vENTILATION AIR

Ventilation Air From Inside Building 

This fresh air would come from an adjoining 

unconfined  space.  When  ventilating  to  an 

adjoining unconfined space, you must provide 

two permanent openings: one within 12" (30.5 

cm) of the ceiling and one within 12" (30.5 cm) 

of  the  floor  on  the  wall  connecting  the  two 

spaces (see options 1 and 2, Figure 2, page 

7). You can also remove door into adjoining 

room (see option 3, Figure 2, page 7). Follow 

the 

National Fuel Gas Code, ANSI Z223.1/

NFPA 54

, Air for Combustion and Ventilation 

for required size of ventilation grills or ducts.

ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills 

or  ducts. You  must  provide  two  permanent 

openings: one within 12" (30.5 cm) of the ceil

-

ing and one within 12" (30.5 cm) of the floor. 

Connect these items directly to the outdoors 

or spaces open to the outdoors. These spaces 

include attics and crawl spaces. Follow the 

Na-

tional Fuel Gas Code, ANSI Z223.1/NFPA 54, 

Air for Combustion and Ventilation for required 

size of ventilation grills or ducts.

DETERMINING FRESH-AIR FLOW 

FOR HEATER LOCATION

Determining if You Have a Confined or 

Unconfined Space

Use this work sheet to determine if you have 

a confined or unconfined space.

Space: 

Includes the room in which you will install 

heater plus any adjoining rooms with doorless 

passageways  or  ventilation  grills  between  the 

rooms.

1.  Determine the volume of the space (length 

x width x height).

 

Length x Width x Height =__________cu. ft. 

(volume of space)

 

Example:

 Space size 20 ft. (6.1m) (length) x 

16 ft. (4.88m) (width) x 8 ft. (2.44 m) (ceiling 

height) = 2,560 cu. ft. (72.49 m

2

)(volume of 

space)

 

If  additional  ventilation  to  adjoining  room 

is supplied with grills or openings, add the 

volume of these rooms to the total volume 

of the space. 

2.  Multiply the space volume by 20 to determine 

the maximum Btu/Hr the space can support.

 

  ________

(volume of space) x 20 = (Maxi

-

mum Btu/Hr the space can support)

 

Example:

 2,560 cu. ft. (72.49 m

2

) (volume of 

space) x 20 = 51,200 (maximum Btu/Hr the 

space can support)

3.  Add the Btu/Hr of all fuel burning appliances 

in the space.

 

Vent-free heater 

 

 _________

Btu/Hr

 

Gas water heater*   

 _________

Btu/Hr

 

Gas furnace 

 

 _________

Btu/Hr

 

Vented gas heater   

 _________

Btu/Hr

 

Gas heater logs 

 

 _________

Btu/Hr

 

Other gas appliances* +  _________

Btu/Hr

 

Total 

 _________

Btu/Hr

 

* Do not include direct-vent gas appliances. 

Direct-vent draws combustion air from the 

outdoors and vents to the outdoors.

 

Example:

 

 

Gas water heater 

 

 _________

Btu/Hr

 

Vent-free heater 

 _________

Btu/Hr

 

Total 

 _________

Btu/Hr

4.  Compare  the  maximum  Btu/Hr  the  space 

can support with the actual amount of Btu/

Hr used.

 

  _______

Btu/Hr (maximum can support) 

 

  _______

Btu/Hr (actual amount used)

 

Example:

  51,200  Btu/Hr  (maximum  the 

space can support) 

 

 

60,000 Btu/Hr (actual amount of 

Btu/Hr used)

AIR FOR COMBUSTION AND VENTILATION

Continued

40,000

60,000

20,000

Содержание GWN10A

Страница 1: ...iance Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the gas supplier INSTALLER Leave this manual with the appliance CONSUMER Retain ...

Страница 2: ...thers These include pregnant women people with heart or lung disease or anemia those under the influ ence of alcohol and those at high altitudes Safety TABLE OF CONTENTS Safety 2 Local Codes 4 Product Identification 4 Unpacking 4 Product Features 4 Air For Combustion and Ventilation 5 Installation 7 Operation 13 Inspecting Heater 15 Cleaning and Maintenance 16 Troubleshooting 17 Specifications 21 ...

Страница 3: ...elight until you provide fresh outside air If heater keeps shutting off have it serviced 9 Do not run heater where flammable liquids or vapors are used or stored under dusty conditions 10 Before using furniture polish wax carpet cleaner or similar products turn heater off If heated the vapors from these products may create a white powder residue within burner box or on adjacent walls or furni ture...

Страница 4: ...n Association Inc Batterymarch Park Quincy MA 02269 State of Massachusetts The installa tion must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit Vent free gas products are prohibited for bedroom and bathroom installa...

Страница 5: ...on Unusually Tight Construction The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation However in buildings of un usually tight construction you must provide additional fresh air Unusually tight construction is defined as construction where a walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of...

Страница 6: ...ms directly to the outdoors or spaces open to the outdoors These spaces include attics and crawl spaces Follow the Na tional Fuel Gas Code ANSI Z223 1 NFPA 54 Air for Combustion and Ventilation for required size of ventilation grills or ducts DETERMINING FRESH AIR FLOW FOR Heater LOCATION Determining if You Have a Confined or Unconfined Space Use this work sheet to determine if you have a confined...

Страница 7: ...as type natural or propane LP for your unit If your gas supply is not correct do not install heater Call dealer where you bought heater for proper type heater WARNING This appliance is equipped for either natural gas or propane LP gas but not both Gas typeisindicatedontheratingplate Field conversion is not permitted INSTALLATION ITEMS Before installing heater make sure you have the items listed be...

Страница 8: ...heater where there is easy access for operation inspection and service in coldest part of room THERMOSTAT SENSING BULB Thermostat Models Only The thermostat sensing bulb is located below the heater Do not move this bulb during instal lation or operation of the heater LOCATING HEATER This heater is designed to be mounted on a wall WARNING Maintain the minimum clearances shown in Figure 4 If you can...

Страница 9: ...rance From Floor Installing Two Mounting Screws Note Wall anchors and mounting screws are in hardware package The hardware package is provided with heater Attaching To Wall Stud Method For attaching mounting bracket to wall studs 1 Drill holes at marked locations using 9 64 drill bit 2 Insert mounting screws into wall studs 3 Tighten screws until 1 16 1 6 mm space thickness of penny is beween scre...

Страница 10: ...Y WARNING This appliance requires a 3 8 NPT National Pipe Thread inlet connection to the pressure regulator WARNING Aqualifiedservice personmustconnectheatertogas supply Follow all local codes WARNING Fornaturalgas never connectheatertoprivate non utility gas wells This gas is commonly knownaswellheadgas IMPORTANT For natural gas check gas line pressure before connecting heater to gas line Gas lin...

Страница 11: ...trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into heater controls If sediment trap is not installed or is installed wrong heater may not run properly IMPORTANT Hold the pressure regulator with wrench when connecting it to gas pip ing and or fittings Do not over tighten pipe connection to regulator The regulator body could be dama...

Страница 12: ...as or using compressed air 4 Check all joints of gas supply piping system Apply a commercial leak detection solution to all joints Bubbles forming show a leak 5 Correct all leaks at once 6 Reconnect heater and equipment shutoff valve to gas supply Check reconnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Fig ure 14 INSTALLATION C...

Страница 13: ... turn by hand don t try to repairit callaqualifiedservicetechnicianor gassupplier Forceorattemptedrepairmay result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS 1 STOP Read t...

Страница 14: ...Instructions page 15 3 With control knob pressed in strike match Hold match to pilot until pilot lights 4 Keep control knob pressed in for 30 sec onds after lighting pilot After 30 seconds release control knob Now follow step 9 under Lighting Instructions page 15 5 Replace front panel Thermostat Control Operation Thermostat models only The thermostatic control used on these models differs from sta...

Страница 15: ...ee To Turn Off Gas to Ap pliance page 14 see Cleaning and Maintenance page 16 Check pilot flame pattern and burner flame patterns often PILOT FLAME PATTERN Figure 20 shows a correct pilot flame pattern Figure 21 shows an incorrect pilot flame pat tern The incorrect pilot flame is not touching the thermocouple This will cause the thermocouple to cool When the thermocouple cools the heater will shut...

Страница 16: ...pilot assembly clean and free of dust and dirt To clean these parts we recommend using compressed air no greater than 30 PSI Your local computer store hardware store or home center may carry compressed air in a can If using compressed air in a can please follow the directions on the can If you don t follow directions on the can you could dam age the pilot assembly 1 Shut off unit including pilot A...

Страница 17: ...4 Air in gas lines when in stalled 5 Depleted gas supply pro pane LP gas 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM When ignitor button is pressed there is no spark at ODS pilot Whenignitorbuttonispressed in thereisasparkatODS Pilot but no ignition REMEDY 1 Replace pilot assembly 2 Replace pilot assembly 3 Reconnect ignitor cable 4 Free ignitor cable if pinched ...

Страница 18: ...ntact local natural or propane LP gas company 1 Contact local natural or propane LP gas company 2 Clean burner see Cleaning and Maintenance page 16 or replace burner orifice 1 Clean burner see Cleaning and Maintenance page 16 2 Replace burner 3 Replace gas regulator POSSIBLE CAUSE 1 Control knob not fully pressed in 2 Control knob not pressed in long enough 3 Equipment shutoff valve not fully open...

Страница 19: ...on 1 Turn heater off when using furniture polish wax carpet cleaners or similar products 1 Turn control knob to 1 posi tion and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum installa tion clearances see Figure 4 page 8 4 Clean burner see Cleaning and Maintenance page 16 or replace burner o...

Страница 20: ... all leaks see Checking Gas Connec tions page 12 1 Open window and or door for ventilation 2 Contact local natural or pro pane LP gas company 3 Clean ODS pilot see Cleaning and Maintenance page 16 1 Locate and correct all leaks see Checking Gas Connec tions page 12 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Gas Connec tions...

Страница 21: ...ion or troubleshooting If so contact FMI PRODUCTS LLC at 1 866 328 4537 When calling please have your model and serial numbers of your heater ready You can also visit our web site at www fmiproducts com Service Hints When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition heater will not produce specified heat propane LP gas supply may be low You may feel your gas p...

Страница 22: ...www fmiproducts com 125326 01A 22 Parts MODELS GWN10A GWP10A GWN10TA GWP10TA VSHN10M VSHP10M VSHN10T VSHP10T 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 4 9 7 8 Manual Models Thermostat Models ...

Страница 23: ...1 Burner Tube 1 104261 01 Burner Tube 1 8 099391 02 Regulator Tube 1 104264 01 Inlet Tube 1 9 099387 17 Pilot Tube 1 099387 11 Pilot Tube 1 10 099317 02 Deflector 1 11 NJF 8C Hex Nut 1 12 104259 01 Orifice 1 104259 02 Orifice 1 104259 05 Orifice 1 104259 06 Orifice 1 13 104263 03 Burner 1 14 120630 03 ODS Pilot 1 120630 02 ODS Pilot 1 15 099318 04 Grill Guard 1 16 099319 02 Top Glass Retainer 1 17...

Страница 24: ...is product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic material labor and incidental costs associated with warranty repairs unless expressly covered by this warranty are not reimbursable under this warranty and are the responsibility of the owner Excluded ...

Отзывы: