background image

 

4

For more information, visit www.desatech.com

 

HEARTH EXTENSION: 

 
A hearth extension is required to protect the combustible floor 
constructed in front of the fireplace.  The hearth extension is 
not included and must be fabricated.  The hearth extension 
must project at least 12 inches beyond each side of the 
fireplace opening (see drawing on front cover). 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The hearth extension must be made of non-combustible, 
inorganic material having an effective thermal conductivity 
“K” of 0.84 BTU IN/FT.HR.F (or less) at 1 inch thick. 
 
Thermal conductivity “K” of materials can be obtained from 
the manufacturer of the non-combustible material.  The 
minimum required thickness for any material could be 
obtained by the following formula: 
 

K factor at 1 inch  = thickness required 

                              0.84 
For example, if the material selected has a K factor of 0.25, 
such as a glass fiber, the following formula would apply: 
 

0.25 = 0.30 thickness required 

                          0.84 
If the hearth extension is to be covered, use non-combustible 
material such as tile, slate, brick, concrete, metal, glass, 
marble, stone etc.  Provide a means to prevent the hearth 
extension from shifting and seal the gap between the fireplace 
frame and hearth extension with a non-combustible material 
(see figure 5). 

 

OPTIONAL OUTSIDE AIR KIT (MODEL AK4E): 
 

The outside air kit must be installed during the rough framing 
of the fireplace due to the nature of its location.  Outside 
combustion air can be accessed through an exterior wall. See 
figure 6 and Accessories on page 11. 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
Avoid installing outside air eyebrow in areas where inlet 
opening may be blocked by snow, bushes or other obstacles.  
It should also be located beyond the reach of children.  The 
maximum height of air inlet above platform of fireplace is 3 ft. 
below the termination flue gas outlet. 
For further details on the installation of the outside air kit, 
please refer to the instructions included with the air kit.  For 
operating instructions please refer to your owner’s manual. 
The outside air handle is located inside the face opening, 
above the upper left top of the rear firebrick (see figure 7).  
Push the rod up to open the air intake and push down to close 
it.  Always open the mechanism when starting a fire to provide 
adequate outside combustion air.  Close the mechanism when 
not in use to prevent cold air from entering the room.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
GAS LINE INSTALLATION (OPTIONAL): 

Gas line hook up should be done by your supplier or a 
qualified service person. 

NOTE:

 Before you proceed, make sure your gas supply is 

turned off. 
 

 WARNING:

 HEARTH EXTENSION IS TO BE 

INSTALLED ONLY AS DESCRIBED. 

 CAUTION:

AIR DUCTS MUST NOT TERMINATE 

IN ATTIC SPACE OR GARAGE. 

Figure 5             HEARTH EXTENSIONS 

Figure 6              AIR KIT INSTALLATION 

Figure 7            AIR KIT DAMPER ROD 

Содержание BAJA 3600

Страница 1: ...approved to ANS Z21 11 2 standard A DESA hood must be installed when using a vent free gas log set See accessories on pg 11 WARNING ALWAYS LEAVE GLASS DOORS FULLY OPENED OR FULLY CLOSED WHEN OPERATING THIS FIREPLACE DESA INTERNATIONAL 2701 INDUSTRIAL DRIVE P O BOX 90024 BOWLING GREEN KY 42102 9004 www desatech com PN 54139 REV C 3 01 SAVE THIS BOOK This book is valuable In addition to instructing ...

Страница 2: ...ALLING THE FIREPLACE PG 3 8 HEARTH EXTENSION PG 4 9 OUTSIDE AIR KIT PG 4 10 GAS LINE INSTALLATION PG 4 11 VENT FREE GAS LOG INSTALLATION PG 5 12 COLD CLIMATE INSTALLATIONS PG 5 13 CHIMNEY PIPE PG 6 7 14 PENETRATING THE ROOF PG 8 15 FLASHING INSTALLATION PG 9 16 STORM COLLAR INSTALLATIONS PG 9 17 TERMINATIONS PG 9 18 FINISHING THE FIREPLACE PG 10 19 MANTEL CLEARANCES PG 10 17 REPLACEMENT AND ACCESS...

Страница 3: ...tinuous operation of this fireplace SELECTING LOCATION To determine the safest and most efficient location for your fireplace consider the following guidelines The location must allow for all proper clearances see page 3 The location should be in a place where the fireplace will not be affected by drafts such as air condition ducts windows or doors A location that avoids the cutting of joists or r...

Страница 4: ...ing flanges touch the side framing STEP 4 Check the level of the fireplace and shim with sheet metal if necessary STEP 5 Before securing fireplace to prepared framing the ember protector provided must be placed between hearth extensions not supplied and under the bottom front edge of the fireplace to protect against glowing embers falling through If the fireplace is to be installed on a raised pla...

Страница 5: ...KIT MODEL AK4E The outside air kit must be installed during the rough framing of the fireplace due to the nature of its location Outside combustion air can be accessed through an exterior wall See figure 6 and Accessories on page 11 Avoid installing outside air eyebrow in areas where inlet opening may be blocked by snow bushes or other obstacles It should also be located beyond the reach of childr...

Страница 6: ...t be installed when using an unvented gas log set see accessories on page 11 VENTED GAS LOG INSTALLATION If you install a decorative gas appliance vented gas log the decorative gas appliance must comply with the Standard for Decorative Gas Appliance for Installation in solid fuel burning fireplace ANS Z21 60 1996 Z21 84 or RGA 2 72 and shall also be installed in accordance with the National Fuel G...

Страница 7: ...e wall pipe segments planned for maximum adaptability to individual site requirements Actual lengths gained lineal gain after fitting overlaps must be taken into consideration see figure 12 Each double wall chimney section consists of a galvanized outer pipe a stainless steel inner flue pipe and a wire spacer The pipe sections must be assembled independently as the chimney is installed When attach...

Страница 8: ...as required by most codes When the double wall pipe passes through a framed opening into an attic space the firestop must be place into the attic floor as in figure 16 When the pipe passes through a framed opening into a living space above the firestop must be placed onto the ceiling from below as shown in figure 16 1 elbow set 16 to 60 ft system height 2 elbow sets 30 to 60 ft system height Figur...

Страница 9: ...termine the correct opening length and flashing required STEP 4 Remove the shingles around the opening measured and cut out this section STEP 5 Add the next sections of the pipe until the end penetrates the roofline Check to see that the proper clearances are maintained Extend chimney by adding sections of double wall pipe until pipe is a minimum of 30 inches above the highest point of the roof cu...

Страница 10: ...lashing or chase and ETL 8DM for chase style termination only Figure 21 shows an RTL 8DM round top termination FOLLOW THE INSTALLATION INSTRUCTIONS PROVIDED WITH THE TERMINATION BEING USED CHASE INSTALLATIONS Instructions for chase installations are included with the chase style termination chosen In a multiple chase installation be sure to provide adequate distance between terminations to prevent...

Страница 11: ...e placed at least 9 inches above the opening of the fireplace see figure 25 Combustible materials above 9 inches and projecting more than 1 inches from the front face of the fireplace must be place at least 12 inches above the fireplace opening Ref NFPA std 7 3 3 3 Mantels or any other combustible material may butt up to the side of the black metal face of the fireplace The clearances from the sid...

Страница 12: ...n visit www desatech com Desa International 2701 Industrial Drive P O Box 90024 Bowling Green KY 42102 9004 www desatech com 800 323 5190 CONTACT YOUR LOCAL DEALER ACCESSORY PARTS CONTACT YOUR LOCAL DEALER REPLACEMENT PARTS ...

Отзывы: