Appendix II – Troubleshooting 

AB06064 · Issue/Rev. 0.0 (5/06

)

  

Page 

11

 

 

Appendix II – Troubleshooting TCP/IP Communications 

 

Troubleshooting an Ethernet Connection 

 

 

 

LED Indicators 

The Link indicator on the Ethernet port (the green LED in top corner of microLoad.net main [MNET] 
board) is a simple indication of the correct wiring of the physical connection. Most PC and router ports 
also have a visible indicator when the connection is wired properly. If the Link light does not 
illuminate, either the cable is the wrong type (i.e. a standard CAT-5 cable was used when a crossover 
cable is needed or vice versa), the cable is faulty, or one of the RJ45 connector plugs is not inserted 
completely into the jack. It is also possible but unlikely that one of the device ports has failed. 
Eliminate the simplest first: double-check that the plugs are inserted fully; and that the cable type is 
correct. You can often verify that a cable is standard (or not) by holding the two connectors from each 
end of the cable together and viewing the wire colors within (most RJ45 connectors are clear plastic). 
If the color pattern on the wires is identical on both ends of the cable, it is a standard cable. 

 

 

 

PING Utility 

To check the connection, Windows and most other network-able computers provide a low-level utility 
called PING that issues a simple ICMP message to a remote device and awaits a response. To use 
this utility in Windows, open a Command Prompt (DOS box) and type the command: 
 

 

 

C:> PING 192.168.0.1 

 

If the connection is successful, PING will report the total time from command to response. If it fails, a 
timeout message will be displayed.

 

 

 

 

Advanced – Ethernet Diagnostic (Packet Sniffer) Utility 

A useful tool for troubleshooting network communications is a 

packet sniffer

. This type of utility 

provides a mechanism to display the traffic being sent/received from the Ethernet port, and to dig 
down to the lower levels to view MAC addresses and IP packet data.  
 
An open source implementation of a packet sniffer utility, Ethereal, is available and can be 
downloaded from the Web at 

http://www.ethereal.com/

. There are versions for Windows, Linux and 

other platforms as well. 

 

Troubleshooting a SLIP Connection 

 

 

Using the Comm Monitor Diagnostic 

The microLoad.net has a built-in diagnostic that displays traffic on the serial communications ports. 
To access the Comm Monitor diagnostic, select Diagnostics Menu from the Main Menu, then scroll 
using the arrow keys until the Comm Monitor selection is highlighted and press <Enter>. Then select 
the communications port (1-3) that was configured for the SLIP connection. By examining the traffic it 
is possible to determine if data is being received from the PC end, and whether a response is being 
issued. You can ‘freeze’ the display, and scroll back and forth, and toggle ASCII and hex mode views 
of the last 255 characters in the communications buffer. 

 

 

 

CLIENT/CLIENTSERVER Handshake 

When establishing a SLIP connection between two devices, Windows uses a non-standard 
handshake to verify the device on the other end of the connection is compatible. Windows opens the 
port and immediately sends the text “CLIENT” out the port, then waits for a response. Only the 
response “CLIENTSERVER” will be accepted by Windows and allow the connection to be made. This 
handshake should happen quickly and it will be visible on the Comm Monitor at least briefly if all is 
functioning properly. If the Comm Monitor shows repeated CLIENT messages with no 
CLIENTSERVER response, it is possible you have the IP addresses incorrect on one side or the  
 
 

Содержание Smith Meter microLoad.net

Страница 1: ... Configuring Windows 2000 XP for Ethernet Connection to microLoad net 3 Section II Configuring a SLIP Connection 5 microLoad Settings for SLIP Communications 5 PC Settings for SLIP Communications 6 Section III Using the TCP IP Link 8 Checking the TCP IP Connection 8 Appendix I Firmware Upgrade Procedure 9 Performing the Firmware Upgrade 9 Appendix II Troubleshooting TCP IP Communications 11 Troubl...

Страница 2: ......

Страница 3: ...the inputting of incorrect or improper program or default values entered in connection with the Smith MeterTM microLoad net Proprietary Notice This document contains information that is proprietary to FMC Technologies Measurement Solutions Inc and is available solely for customer information The information herein shall not be duplicated used or disclosed without prior permission of FMC Measuremen...

Страница 4: ......

Страница 5: ...reserved by the standard for special features such as broadcasting A very large class A network has an 8 bit net mask leaving 24 bits to specify the host Hence this type of network can have a huge number of host machines 224 over 16 million computers but there can only be 255 of those types of networks in existence since there are only 255 unique network IDs that can be made from 8 bits So why spe...

Страница 6: ... Program Com Link Level 3 Return to the Main Menu using the Clear key Note If using the microLoad net s Ethernet port make sure that none of the microLoad net serial communications ports are configured to the SLIP TCP IP function configuring a SLIP connection will disable the Ethernet connection It is recommended that the microLoad net be installed to a private network not connected directly to th...

Страница 7: ...rossover cable or connecting both the PC and the microLoad to a multi port network device such as a hub switch or router If using a crossover cable plug one end of the cable into the Ethernet port on the PC If using a hub connect the PC s Ethernet port to one of the router s ports using a standard cable At the microLoad net remove the cover and find the CAT 5 connector CN8 on the back of the MNET ...

Страница 8: ...ted then click Properties Select Use the following IP address Enter an IP address on the same network as the microLoad i e 192 168 0 10 Make sure the host address is different than the microLoad net Enter the subnet mask 255 255 255 0 Click OKAY when finished Click OKAY again to exit the Local Area Connection dialog Continue with the section titled Establishing and Verifying a Successful Connectio...

Страница 9: ...eriod ie RAM and ROM test Press Enter from the ready screen to access the Main Menu Once in the Main Menu screen select Program Mode Menu and press Enter Enter the access code when prompted and press Enter Select Comm Directory and Press Enter from the Program Mode Menu From Comm Directory select the Comm Port Config and press Enter Select Comm 1 and press Enter From Comm 1 Directory select the fo...

Страница 10: ...ng identifiably unique o Select Communications cable between two computers Com 1 when the wizard prompts for a device selected Click Next o Click on Anyone s Use for connection availability Click Next o Click Finish on the Confirmation page of the Wizard Upon completion a new screen will pop up automatically with the title Connect to microLoad via SLIP Click Properties o In the General tab select ...

Страница 11: ...elect Internet Protocol TCP IP in the list box and click Properties A new window will appear that is labeled Internet Protocol TCP IP Properties o Select Use the following IP address o Specify an address that is DIFFERENT from but on the same subnet as the microLoad you are using For example if the microLoad is configured for 192 168 0 1 set the PC to 192 168 0 5 or 192 168 0 10 etc Click OK to ex...

Страница 12: ...nnection was successful this will occur if the microLoad net is in program mode via the keypad or configured so that Program Mode access through communications is disabled If the microMate application times out and fails to connect consult Appendix II Troubleshooting for assistance with debugging the connection With the microMate you can read and write program codes use the Terminal Emulator to se...

Страница 13: ...l nonvolatile memory in the microLoad configuration reports equations etc continue IMPORTANT BE SURE YOU HAVE SAVED A COPY OF THE PROGRAM CODE CONFIGURATION BEFORE PROCEEDING ALONG WITH SAVING ANY ADDITIONAL CONFIGURATION ITEMS SUCH AS ONFIGURABLE REPORTS USER EQUATIONS ETC IN USE Select OK to continue the upgrade process or Cancel to abort If the PC running microMate has an Internet connection th...

Страница 14: ...owing microLoad net to boot into RAM Executive please wait will be displayed Select OK when prompted to begin the download You will see the following text displayed on the microMate o Erasing existing application memory flash o Initiating application image download o Downloading image The download process may take from 2 to 10 minutes SLIP is usually significantly slower than Ethernet When the dow...

Страница 15: ...y A useful tool for troubleshooting network communications is a packet sniffer This type of utility provides a mechanism to display the traffic being sent received from the Ethernet port and to dig down to the lower levels to view MAC addresses and IP packet data An open source implementation of a packet sniffer utility Ethereal is available and can be downloaded from the Web at http www ethereal ...

Страница 16: ... Upgrade Firmware The microMate will attempt to retrieve the latest firmware image from the Internet and place it in the application directory You can perform this operation from any Internet enabled PC it does not have to be connected to the microLoad net for the firmware retrieval process portion of the upgrade to be performed Automated Upgrade Process Fails Unable to Locate Firmware Image This ...

Страница 17: ...Appendix II Troubleshooting AB06064 Issue Rev 0 0 5 06 Page 13 ...

Страница 18: ...rgentina Phone 54 11 4312 4736 Integrated Measurement Systems Corpus Christi TX USA Phone 361 289 3400 Kongsberg Norway Phone 47 32 286 700 San Juan Puerto Rico Phone 787 274 3760 United Arab Emirates Dubai Phone 971 4 331 3646 Liquid Measurement Products Erie PA USA Phone 814 898 5000 Los Angeles CA USA Phone 661 702 8660 Slough England Phone 44 1753 57 1515 Ellerbek Germany Phone 49 4101 3040 Ba...

Отзывы: