Section II - Operations
6
MN06065 Rev. 0.3 (8/97)
Additive Injector Selection
Stand-alone Mode
When the AccuLoad II Ratio Blender is in the Stand-
alone mode of operation the additive selection can be
programmed to be either automatic or manual, de-
pending on how code 804 of the Systems Directory
has been programmed.
Code
Description
804
Manual/Auto Additive Injector option must be
programmed to either:
Zero for auto injectors - the additive outputs
that are programmed in the AccuLoad II will
automatically be selected for each batch.
One for manual injectors in the standby mode
only at the beginning of each transaction.
Two for manual injectors prompting at the
beginning of each transaction.
Three for manual injectors prompting at the
beginning of each batch.
The operation will be as follows for manual selection
(code 1, 2 or 3):
The following examples show the left-hand display
only.
1. Select recipe.
2. The driver or operator is required to enter a rec-
ipe number (1 through 24). The display will read:
Select Recipe 1
where 1 is the recipe number entered by the
driver or operator.
3. After the recipe has been selected press "EN-
TER". The following will be displayed:
Midgrade Recipe No 01
Where:
Midgrade = The programmed recipe name.
01
= The recipe number selected by the
operator.
4. If the correct recipe is displayed press "ENTER".
The display will read:
Select Injector #1 0 = Off
5. The driver or operator is required to enter a “1” to
select the additive. If selected the display would
read:
Select Injector #1 1 = On
Note: If an error was made in selecting the additive to be "on",
pressing "CLEAR" will select the additive "off".
6. After additive injector #1 has been selected to
either "on" or "off" press "ENTER". The following
will be displayed:
Select Injector#2 0 =Off
7. The driver or operator repeats steps 2 and 3 until
all the programmed additive outputs have been
selected as either "ON" or "OFF". Press "EN-
TER" to store the additives that have been se-
lected. The display will read:
Injectors on = #1,2,3,4,5,6,7,8
Indicating which of the additive outputs have been
selected. If none of the additives have been selected
the display will read:
No Injectors Selected
Note: If the selections are incorrect press "CLEAR" and the original
display will be displayed (see step 1) and the process can begin
again.