background image

14.

 

Connect  power  cord  wires  to  terminals  in  panel,  or  connect  power  source,  and  check  pump  running.    Motor 
should run smoothly and be free of vibration. 

 

Pump does not run or hum. 

1.

 

Line circuit breaker may be off, or fuse, if used, may be blown or loose. 

2.

 

Water level in sump may be too low.  Run in more water. 

3.

 

Pump cord plug may not be making contact in receptacle. 

4.

 

If pump is using the series cord plug, the two plugs may not be plugged tightly together. 

5.

 

Float may be stuck.  Be sure float operates freely in basin. 

6.

 

If all symptoms check OK, motor winding may be open; take to service center for check. 

 

Pump runs but does not deliver water.

 

 
1.

 

Check valve may be installed backward.  Arrow in valve points in direction of flow. 

2.

 

Discharge gate valve, if used, may be closed. 

3.

 

Pump may be air locked.  Start and stop several times by plugging and unplugging cord.  Check vent hole in 
pump case for plugging. 

4.

 

Pump head may be too high.  Pump cannot deliver water over (SPD50H) 50’ or (SPD100H) 64’ vertical.  Pump 
must be sized to operating conditions. 

5.

 

Inlet in pump base may be clogged.  Remove pump and clean out openings. 

6.

 

Impeller or volute openings may be plugged or partially plugged.   Remove pump and clean per maintenance 
instructions. 

 

Pump runs and pumps out sump but does not stop.

 

 
1.

 

Float is stuck in 

up 

position.  Be sure float operates freely in basin.  Diaphragm vent tube in power cord may be 

blocked or bent.  Clear obstruction. 

 

Pump runs but delivers only small amount of water.

 

 
1.

 

Pump may be air locked.  Start and stop several times by plugging and unplugging cord.   Check vent hole in 
pump case for plugging. 

2.

 

Pump  head  may  be  too  high.    Pump  cannot  deliver  water  over  (SPD50H)  50’  or  (SPD100H)  64’  vertical.  
Horizontal distance does not affect pumping, except loss due to friction. 

3.

 

Inlet in pump base may be clogged.  Remove pump and clean out openings. 

4.

 

Impeller or volute openings may be plugged.  Remove pump and clean. 

5.

 

Pump impeller may be partially clogged causing motor to run slow, resulting in motor overload. 

 

Fuse blows or circuit breaker trips when pump starts.

 

 
1.

 

Inlet in pump base may be clogged.  Remove pump and clean out openings. 

2.

 

Impeller or volute openings may be plugged or partially plugged.  Remove pump and clean. 

3.

 

Pump impeller may be partially clogged causing motor to run slow, resulting in motor overload. 

4.

 

Fuse size or circuit breaker is too small. 

5.

 

Defective motor stator: return to authorized Hydromatic service center. 

 

Motor runs for short time, stops, the after short period starts again.  Indicates overload caused by symptom 
shown.

 

 
1.

 

Inlet in pump base may be clogged.  Remove pump and clean out openings. 

2.

 

Impeller or volute openings may be plugged or partially plugged.  Remove pump and clean. 

3.

 

Pump impeller may be partially clogged causing motor to run slow, resulting in motor overload. 

4.

 

Defective motor stator, return to Hydromatic service center. 

 
If symptom is not found on chart, call authorized Hydromatic distributor or repair center for assistance. 
 

Содержание MP-3067

Страница 1: ...yelids apart with your fingers Contact an eye specialist On your skin Remove contaminated clothes Wash your skin with soap and water Seek medical attention if required Make sure the pump cannot roll o...

Страница 2: ...has been an increase leakage Note Air oil mixture can be confused with water oil mixture Insert a tube or hose into the oil hole Cover the top end of the tube and take up a little oil from the bottom...

Страница 3: ...ective equipment Rotation direction of pump Transpose two phase leads if the impeller does not rotate requires voltage clockwise as viewed from above Rotation in the wrong direction reduces the capaci...

Страница 4: ...impeller and tighten the impeller screw 6 Check that the impeller can be rotated by hand 7 Fit the motor section to the pump casing Make sure that the pump casing has the right orientation Troublesho...

Страница 5: ...continuity and are tight Is the start relay or the Yes Replace start capacitor defective only for 1 phase motor No Is the impeller stuck Yes Clean WARNING disconnect Clean the sump power before check...

Страница 6: ...the pump able to empty No Check the station to the stop level for leakage in pipe and or discharge connection Yes that the impeller is not clogged WARNING disconnect power before checking the impelle...

Страница 7: ...hase motor Yes Is the run capacitor defective Yes Replace Only for 1 phase motor No Contact service shop 5 Pump runs but delivers too little or no water Check direction of rotation pump that valves ar...

Страница 8: ...y in running water for 15 minutes Hold your eyelids apart with your fingers Contact an eye specialist On your skin Remove contaminated clothes Wash your skin with soap and water Seek medical attention...

Страница 9: ...ater again the fault may be that an oil screw is not sufficiently tight that an oil screw O ring or its sealing surface is damaged that an O ring or its sealing surface is damaged that the lower seal...

Страница 10: ...also removed 4 Fill up with 1 06 quarts 3102 2 45 quarts 3127 of new oil OIL IN Always replace the O rings under the oil casing screw Put the screws back and tighten them Use the following oil or thei...

Страница 11: ...sher to be screwed onto the shaft end Press the impeller onto the shaft with the impeller screw and tighten to the right torque Check that the impeller can be rotated by hand Fit the motor section to...

Страница 12: ...ned satisfactorily Electrical work shall be performed by an authorized electrician Follow local safety regulations and observe recommended safety precautions 1 Pump fails to start Is an alarm signal i...

Страница 13: ...ght the impeller If anything else is wrong contact service shop No Is the installation receiving No Notify an electrician full voltage on all three phases Yes Are the phase currents Yes Contact servic...

Страница 14: ...start due to Yes Check backflow which fills sump to that the distance between the start and stop start level again levels is not too small the non return valve s No that the riser is not too long with...

Страница 15: ...in the problem could be a pump or piping is clogged b pump motor or bearings may be defective c start capacitor in motor may have failed d pump may be misfired to terminal block e head is lower than r...

Страница 16: ...ohmmeter With ohmmeter scale set at R x 1000 attach meter leads to capacitor The meter needle should go to zero and come back slowly If it does not the capacitor should be replaced 6 To check motor s...

Страница 17: ...or housing This is a paraffin SE 40 process oil The same oil is used in the seal housing between the two mechanical seals To check the seals remove the lower housing pipe plug and pour the oil out int...

Страница 18: ...mic of the stationary seal half 5 Replace the stator if it is visibly burned or if the ground resistance test or the winding resistance test has failed Note that the replacement stator must be of the...

Страница 19: ...be blocked or bent Clear obstruction Pump runs but delivers only small amount of water 1 Pump may be air locked Start and stop several times by plugging and unplugging cord Check vent hole in pump cas...

Страница 20: ...e water does not pump down stop the pump and close the valve in the discharge line Lift the pump until the sealing flange just clears the sealing face to allow trapped air to be vented Lower the pump...

Страница 21: ...ld not require replacement until you replace the bearings or generally rebuild the motor due to normal wear 1 Remove cutters impeller and pump parts as described under Replacing Grinder Parts NOTE Whe...

Страница 22: ...ring fill process to eliminate trapped air Insert bearing housing into stator and over shaft using care with placement of O rings Some fluid will be displaced by the bearing housing assuring complete...

Страница 23: ...nd clip to wires to be tested d Attach ohmmeter leads to motor leads per chart below and compare readings e A reading more than three times shown indicates a possible burned open winding or a loose co...

Страница 24: ...res are connected at the panel terminal block Warranty is void if wires are not connected or are jumped CAUTION The single phase 4WHV and V4WHV pumps with automatic heat sensor rest will restart witho...

Страница 25: ...he impeller on the shaft be sure the mechanical seal and its spring are in place 3 Position retaining washer with long pin extension in keyway 4 Obtain a new lockwasher and flatten two tabs located 18...

Страница 26: ...ift arm on check valve to vent off air Also check that the 5 32 vent hole in the volute is open Circuit breaker trips 1 Reset breaker by pushing clear down on handle then back to on position If breake...

Страница 27: ...AY FROM GRINDER IMPELLER WHEN MAKING THIS CHECK If 3 phase rotation is wrong interchange any two line leads at he control box to reverse motor CAUTION BE SURE CONNECTED POWER AGREES WITH DATA ON PUMP...

Страница 28: ...imes to purge air 2 Run additional water into basin so that pump will be submerged deeper to clear water 3 If pump is three phase rotation may be wrong 4 If air does not clear it may be necessary to l...

Страница 29: ...the motor 2 Grinder impeller may be rubbing on wear ring due to a bent shaft or misalignment Grease and solids have accumulated 1 Lower weight of level switch may be set too high Set around pump and w...

Страница 30: ...of impeller cutter vanes should extend about 1 8 below bottom of shredding ring If more than 1 8 extends below ring it means pump impeller has loosened Remove grinder impeller and ring as described ab...

Страница 31: ...with these pumps Do not install or remove pump with person s in basin GENERAL 1 Most accidents can be avoided by using common sense 2 Do not wear loose clothing that can become entangled in the impell...

Страница 32: ...er reading but if pump is out of service and reading is below 500 000 ohms the motor housing and stator should be removed and baked in a drying oven at 220 F To be serviced only at authorized service...

Страница 33: ...ced capacity 4 Gate valve or check valve may be clogged causing low pump flow 5 Pump may be air logged Circuit breaker trips 1 Reset breaker by pushing clear down on handle then back to on position If...

Страница 34: ...dding ring If more than 1 8 extends below ring it means pump impeller has loosened and if it is less it means the shredding ring is not properly seated If the pump impeller has loosened remove grinder...

Отзывы: