Test the Connections
Test communication
Follow these steps to test communication.
Table 14
Step
Action
Check OK
1
Check that the cables to the modem are connected securely.
2
Check the supply voltage to an external modem.
3
Check the communication led on the front panel. These should flash when the
unit is transmitting and receiving data.
4
Check the modem led to determine if the modem is transmitting and receiving
data.
Reference: See the modem manual for details.
5
If a modem with a dialup connection between RTU and central system is used,
then check the telephone connection by
• connecting a telephone in parallel with the RTU
• calling another number to test the connection
• calling the RTU from an ordinary telephone to test if the RTU answers.
Test level sensor signal
Follow these steps to test level sensor signal.
Table 15
Step
Action
Check OK
1
Check for a voltage of at least 6V DC across the terminals.
2
• Lift the sensor out of the water and check that it is delivering a 4 mA current
signal.
• Check that the signal changes when the sensor is again immersed in water.
Test digital inputs
To test digital inputs
• activate a signal, such as a motor protection, and
• check that the led for the input is lit.
Test supply voltage
Follow these steps to test supply voltage.
Table 16
Step
Action
Check OK
1
Check the power supply unit connections.
2
Measure the supply voltage at the terminal block and check that it is within the
specified range.
Test the Connections
Hardware for APP700 and APX700 Installation
19