DTX-MFM2/GFM2/SFM2 Fiber Modules
Users Manual
20
About Method B Connections
The reference and test connections shown in this manual
produce Method B results. Method B results include the
loss of the fiber plus the loss of the connections at both
ends of the link. To ensure accurate results, the
connection to the fiber module's output port must not be
disconnected after the reference is set. Using connector
adapters that match the connectors in the fiber under test
lets you connect to the fiber without disturbing the
output port connection.
W
Caution
If you disconnect the reference test cords from
the tester’s or smart remote’s output port after
setting the reference, you must set the reference
again to ensure valid measurements.
If you do not have the correct connector adapters, see
Appendix B, "Modified Method B" for alternative
connections that produce Method B results.
To test links with different connectors at each end, see
the alternate method described in the Appendix of the
DTX Series CableAnalyzer Technical Reference Handbook
or visit the Fluke Networks Knowledge Base for
suggestions.
Содержание DTX-GFM2
Страница 15: ...Installing the Connector Adapter 9 amd99f eps Figure 4 Installing the Connector Adapter...
Страница 29: ...Certifying Fiber Cabling 23 amd145f eps Figure 8 Smart Remote Mode Reference Connections Method B...
Страница 31: ...Certifying Fiber Cabling 25 amd146f eps Figure 9 Smart Remote Mode Test Connections Method B...
Страница 35: ...Certifying Fiber Cabling 29 amd147f eps Figure 11 Loopback Mode Reference Connections Method B...
Страница 37: ...Certifying Fiber Cabling 31 amd148f eps Figure 12 Loopback Mode Test Connections Method B...
Страница 41: ...Certifying Fiber Cabling 35 amd149f eps Figure 14 Far End Source Mode Reference Connections Method B...
Страница 45: ...Using the Visual Fault Locator 39 amd23f eps Figure 17 Using the Visual Fault Locator...
Страница 48: ...DTX MFM2 GFM2 SFM2 Fiber Modules Users Manual 42 amd58f eps Figure 19 Connections for Monitoring Optical Power...
Страница 60: ...DTX MFM2 GFM2 SFM2 Fiber Modules Users Manual B 4...