![Fluke 1623 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/fluke/1623/1623_user-manual_2310313026.webp)
Fluke 1623
Users Manual
18
Automatic range selection.
Measurement is not performed if the current through the current clamp is too
low.
R
A
4-pole ground resistance measurement
(IEC 1557-5)
Switch
position
Resolution
measuring range Intrinsic error
Operating error
Ra 4-pole
0,001 … 10
Ω
0,001
Ω
...
19,99 k
Ω
±
(2% rdg + 3 d)
±
(5% rdg +
3 d)
Measuring principle: Current/voltage measurement
Measuring voltage:
Um = 48 Vac.
Short-circuit current:
> 50 mA
Measuring frequency:
128 Hz (125 Hz on request)
Probe resistance (Rs+ Res):
max. 100 k
Ω
Auxiliary earth electrode resistance
(Rh):
max. 100 k
Ω
Additional error from Rh and Rs:
Rh[k
Ω
]
x
Rs[k
Ω
/Ra[
Ω
]
x
0,2 %
Monitoring of Rs, and Rh with error indicator.
Automatic range selection.
R
A
3-pole selective ground resistance measurement with current clamp
(R
A
A
)
Switch
position
Resolution Measuring range Intrinsic error
Operating error
Ra 3-pole
A
0.001 ...
10
Ω
0.001
Ω
..
19.99 k
Ω
±
(7% rdg + 3 d)
±
(10% rdg + 5 d)
Measuring principle: Current/voltage measurement (with external current
clamp)
Measuring voltage:
Um = 48 VAC.
Short-circuit current:
> 50 mA
Measuring frequency:
128 Hz (125 Hz on request)
Shop for Fluke products online at:
1.877.766.5412
www.
MyFlukeStore
.com
Содержание 1623
Страница 4: ...1623 Users Manual ii Shop for Fluke products online at 1 877 766 5412 www MyFlukeStore com ...
Страница 6: ...Users Manual iv Shop for Fluke products online at 1 877 766 5412 www MyFlukeStore com ...
Страница 8: ...Users Manual vi Shop for Fluke products online at 1 877 766 5412 www MyFlukeStore com ...
Страница 30: ...Fluke 1623 Users Manual 22 Shop for Fluke products online at 1 877 766 5412 www MyFlukeStore com ...