Earth/Ground Tester
Setup
11
R
A
4-pole Selective Earth Resistance Measurement with
Current Clamp
The R
A
4-pole Selective Earth Resistance Measurement with Current Clamp
procedure is useful for measuring the resistance of different parallel sections of
an earth/ground system. Refer to Figure 7.
A
Select function R
A
4-pole
A
.
Display as shown below.
B
Connect test leads.
Connect terminals E/C1 and ES/P1 with the supplied safety test leads
(1.5 m) to the earth electrode to be measured. Place 2 ground stakes
in earth/dirt. Minimum distance between earth electrode (E/C1),
probe (S/P2) and auxiliary earth (H/C2) should be at least 20 m! The
ES test lead eliminates the influence of the test leads.
Connect stakes with 25 m and 50 m wires to H/C2 and S/P2 as
shown.
Connect current clamp with adapter cable as shown.
C
Press
START.
The “active” symbol indicates that measurement is in progress. For
continuous measurement keep START pressed.
D
Symbol
“
9
” indicates completed measurement. The result is kept on
display until a new measurement is started or the rotary switch is
turned.
E
H
S
e
v
i
t
c
a
S
E
H
s
u
l
p
V
0
5
x
a
m
2
P
S
1
P
S
E
S
E
S
E
S
E
E
H
S
FLUKE
1
2
3
4
edv006.eps
Figure 7. R
A
4-pole Selective Earth Resistance Measurement with Current
Clamp
Shop for Fluke products online at:
1.877.766.5412
www.
MyFlukeStore
.com
Содержание 1623
Страница 4: ...1623 Users Manual ii Shop for Fluke products online at 1 877 766 5412 www MyFlukeStore com ...
Страница 6: ...Users Manual iv Shop for Fluke products online at 1 877 766 5412 www MyFlukeStore com ...
Страница 8: ...Users Manual vi Shop for Fluke products online at 1 877 766 5412 www MyFlukeStore com ...
Страница 30: ...Fluke 1623 Users Manual 22 Shop for Fluke products online at 1 877 766 5412 www MyFlukeStore com ...