Set the sensor supply
1. Make the F126-P safe. If applicable, mind the battery power.
2. Open the F126-P and carefully remove the cable-connectors and the protective cover.
3. Find and set the switches and select the V
out
as required.
4. Close the protective cover and install the cable connectors.
5. Close the F126-P.
Risk of electrocution - High voltage!
Make sure, all the leads to the terminals are disconnected from the F126-P and NEVER
connect the mains power supply to the unit when the protection cover has been removed!
Type PD
Power supply in:
8-24V AC / 10-30V DC
Switch location (typical)
Sensor
V
out
selection
Sensor supply out
A
1
2
3
4
NOTE: Use an AC
autotransformer (spartrafo)
with galvanic isolation.
int
-
off
off
Coil 1.2V DC; <1mA
Reed 3V DC; <1mA
ext
-
on
on
off
on
off
off
8.2V DC @8V
in
AC / 10V
in
DC
12V DC @10V
in
AC / 14V
in
DC
24V DC @18V
in
AC / 26V
in
DC
Type PF
Power supply in
:
15-24V AC / 20-30V DC
Switch location (typical)
Sensor
V
out
selection
Sensor supply out
A
1
2
3
4
int
-
off
off
Coil 1.2V DC; <1mA
Reed 3V DC; <1mA
ext
-
on
on
off
on
off
off
8.2V DC @8V
in
AC / 10V
in
DC
12V DC @10V
in
AC / 14V
in
DC
24V DC @18V
in
AC / 26V
in
DC
Type PM
Power supply in
: 115V - 230V AC
Switch location (typical)
Sensor
V
out
selection
Sensor supply out
A
1
2
3
4
int
-
off
off
Coil 1.2V DC; <1mA
Reed 3V DC; <1mA
ext
-
on
on
off
on
off
off
8.2V DC
12V DC
24V DC
Fig. 9: Sensor supply voltage - Switch setting
Terminal 00-01; basic POWER SUPPLY - type PX
Connect an external power supply of 8-30VDC to these terminals
. Do connect the “-“ to terminal 00
and the “+” to terminal 01. When power is applied to these terminals, the (optional) internal battery
will be disabled / enabled automatically to extend the battery life time.
Terminal 05-06; scaled pulse output R1:
Setup A (read chapter 3) determines the pulse output function. The maximum pulse frequency of
this output is 500Hz. If a relay output option has been supplied, be sure that the output frequency
does not exceed 5Hz or else the life-time of the relay will be reduced significantly.