3. CONFIGURATION 

 

3.1. INTRODUCTION 

 
This and the following chapters are exclusively meant for electricians and non-operators. In these, 
an extensive description of all software settings and hardware connections are provided. 
 

Mounting, electrical installation, start-up and maintenance of the instrument may only be 

carried out by trained personnel authorized by the operator of the facility. Personnel must 
read and understand this Operating Manual before carrying out its instructions. 

The F110-A may only be operated by personnel who are authorized and trained by the 
operator of the facility. All instructions in this manual are to be observed. 

Ensure that the measuring system is correctly wired up according to the wiring diagrams. The 

housing may only be opened by trained personnel. 
Take careful notice of the " Safety rules, instructions and precautionary measures " in the 

front of this manual. 

 
 

3.2. PROGRAMMING 

SETUP-LEVEL 

 

3.2.1. GENERAL 

 
Configuration of the F110-A is done at 

SETUP

-level. 

SETUP

-level is reached by pressing the 

PROG/ENTER key for 7 seconds; at which time, both arrows 

 will be displayed. In order to return 

to the operator level, PROG will have to be pressed for three seconds. Alternatively, if no keys are 
pressed for 2 minutes, the unit will exit 

SETUP

 automatically. 

SETUP

 can be reached at all times while the F110-A remains fully operational. 

 

Note:

 A pass code may be required to enter SETUP. Without this pass code access to SETUP is 

denied. 
 

 

 
To enter SETUP-level: 

 

 

 

 

Содержание F110-A

Страница 1: ...meter 0 4 20mA Signal outputs 0 4 20mA 0 10V ref flowrate and pulse ref total Options Intrinsically Safe Modbus communication external reset and backlight F Series Field mounted indicators for safe an...

Страница 2: ...of according to local regulations regarding waste electronic equipment If a battery is present in this product it should be disposed of separately The separate collection and recycling of your waste e...

Страница 3: ...edures which if not performed correctly may lead to personal injury a safety hazard or damage of the F110 A or connected instruments A caution indicates actions or procedures which if not performed co...

Страница 4: ...18 7 Relay output 19 8 Communication optional 20 9 Others 20 4 Installation 21 4 1 General directions 21 4 2 Installation surrounding conditions 21 4 3 Dimensions Enclosure 22 4 4 Installing the hard...

Страница 5: ...transmitting possibilities with analog pulse and communication option outputs Flowmeter input This manual describes the unit with a 0 4 20mA input from the flowmeter A version Other versions are avai...

Страница 6: ...ns as described in chapter 3 2 3 Display information The unit has a large transflective LCD with all kinds of symbols and digits to display measuring units status information trend indication and key...

Страница 7: ...tion is meant for users operators 2 2 CONTROL PANEL The following keys are available Fig 2 Control Panel Functions of the keys This key is used to program and save new values or settings It is also us...

Страница 8: ...d The arrows indicate the increase decrease of the flowrate trend Clear total The value for total can be re initialized To do so press CLEAR twice After pressing CLEAR once the flashing text PUSH CLEA...

Страница 9: ...re to be observed Ensure that the measuring system is correctly wired up according to the wiring diagrams The housing may only be opened by trained personnel Take careful notice of the Safety rules in...

Страница 10: ...nique number which is displayed below the word SETUP at the bottom of the display The number is a combination of two figures The first figure indicates the function group and the second figure the sub...

Страница 11: ...a is altered but ENTER is not pressed then the alteration can still be cancelled by waiting for 20 seconds or by pressing ENTER for three seconds the PROG procedure will be left automatically and the...

Страница 12: ...ec 30 sec off 42 BATTERY MODE operational shelf 5 FLOWMETER 51 FORMULA interpolation square root 52 FILTER 00 99 53 CUT OFF 0 0 99 9 54 CALIBRATE LOW default calibrate calibrate set 55 CALIBRATE HIGH...

Страница 13: ...whole numbers decimals are set with SETUP 14 The more accurate the span the more accurate the functioning of the system will be Example 1 Calculating the Span Let us assume that the flowmeter generat...

Страница 14: ...span the flowmeter signal is converted to a quantity The span for flowrate is determined on the basis of the selected measurement unit and time unit at 20mA or maximum signal Enter the span in whole...

Страница 15: ...strongly advised to select a slow refresh rate Please understand that NO information will be lost the signal will be processed and the output signals will be generated in the normal way The following...

Страница 16: ...et to a desired value The filter principal is based on three input values the filter level 01 99 the last measured analog value and the last average value The higher the filter level the longer the re...

Страница 17: ...d CALIBRATE with this setting the input will be calibrated with the actual 0 4mA value After pressing enter CAL SET will be displayed as soon as the calibration is completed From that moment the analo...

Страница 18: ...current will be the minimum signal 0 4mA or 10V Examples 4MA SETUP 62 20MA SETUP 63 CUT OFF SETUP 64 REQUIRED RATE OUTPUT 0 L min 100 L min 2 100 0 2 2 0 L min 4 16 2 4 32mA 20 L min 800 L min 3 5 80...

Страница 19: ...seconds 7 RELAY OUTPUT One transistor or mechanic relay output is available as scaled pulse output according to the accumulated total PERIOD TIME PULSE OUTPUT 71 The period time determines the time t...

Страница 20: ...f the F110 A Your supplier will ask for this information in the case of a serious breakdown or to assess the suitability of your model for upgrade considerations VERSION SOFTWARE 92 For support and ma...

Страница 21: ...contact is no longer assured when the housing cover is removed or the panel cabinet has been opened danger from electrical shock The housing may only be opened by trained personnel Take careful notice...

Страница 22: ...mm 30mm 22 5mm M20 x 1 5 M16 x 1 5 M16 x 1 5 30mm 30mm 22 50mm M20 x 1 5 22 5mm M20 x 1 5 M20 x 1 5 25mm 25mm 22 5mm 1 2 NPT 0 9 3x 1 2 NPT 0 12 0 12 0 9 HA HM HN HO HP HT HU 6 x M12 12mm 12mm 24mm 24...

Страница 23: ...box flat bottom HE HF HG HH D 12mm 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 22 5mm 30mm 30mm D 16mm D 20mm 0 9 D 22mm 0 866 22 5mm 25mm 25mm D 20mm D 20mm D 16mm HC 75 mm 2 95 118 mm 4 65 104 mm 4 09...

Страница 24: ...ue to impact or friction sparks between the enclosure and iron steel is excluded Do ground the aluminum enclosure properly as indicated if the F110 A has been supplied with the 115 230V AC power suppl...

Страница 25: ...ll the leads to the terminals are disconnected from the unit when the internal plastic protection cover has been removed HIGH VOLTAGE 400V NEVER connect the mains power supply to the unit when the pla...

Страница 26: ...A and options REMARKS TERMINAL CONNECTORS Terminal GND 01 02 Power Supply only available with type PD PF or PM TYPE SENSOR SUPPLY Terminal backlight T YPE AA T YPE AU Type OA Type OR GND 01 02 PD 8 24...

Страница 27: ...lse signal output is available with this option Max driving capacity 50mA 24V per output Requires power supply type PD PF PM Type OR A mechanical relay output is available with this option Max switch...

Страница 28: ...y valid for standard passive output type AP Terminal 07 08 analog output SETUP 7 An analog output signal proportional to the flowrate is available as standard Type AA An active 4 20mA signal proportio...

Страница 29: ...C This option can be used with a battery powered unit but the life time of the battery is about 2 3 years Type AP A passive 4 20mA signal proportional to the flowrate is available with this option Whe...

Страница 30: ...mA flowmeter signal which has a double function The signal will be processed 4 times a second with a 14 bits accuracy and the unit will be powered from the sensor signal input loop powered The input i...

Страница 31: ...Terminal 26 31 backlight type ZB option Note if the unit is supplied with a power supply type PD PF or PM the backlight supply is integrated so the text following is not applicable To power the backl...

Страница 32: ...ns and precautionary measures in the front of this manual Safety Instructions When two or more active intrinsically safe circuits are connected to the indicator in order to prevent voltage and or curr...

Страница 33: ...dicator is either supplied by the internal supply option PC or the external supply connected to terminals 0 and 1 option PD or the circuit supply connected to terminals 7 and 8 option AP The maximum v...

Страница 34: ...00 Ohm 30V DC Note It is required to link the minus from the analog output terminal 7 with a ground terminal of the unit terminal GND 3 5 9 12 or 15 Type PD Intrinsically Safe power supply and sensor...

Страница 35: ...A AP IB CT OT PD XI Please note power supply type PD is not required unit is output loop powered type AP Pulse output type OT passive transistor Ci is negligibly small Ci is negligibly small e g indic...

Страница 36: ...Status input type IB Ci is negligibly small 12 13 Common ground RXD Common ground TXD 28 26 29 DTR 12V 27 e g PC 3 2V low pass filter 1M Modbus communication type CT TTL Please note communciation type...

Страница 37: ...ed Ex label are certified for replacement and use in hazardous areas Batteries for use in safe areas have no Ex label DO NOT EXCHANGE Using the wrong type of battery can pose a SERIOUS RISK For use in...

Страница 38: ...such a way that no condensation will occur for example by placing dry silica gel sachet in the casing just before closing it Furthermore it is required to replace or dry the silica gel periodically as...

Страница 39: ...pe HU Type HZ GRP enclosures Type HD Type HE Type HF Type HG Type HH Dimensions 130 x 120 x 75mm 5 10 x 4 72 x 2 95 LxHxD IP67 NEMA4X Drilling 2x PG9 1x M20 Drilling 2x M16 1x M20 Drilling 1x M20 Dril...

Страница 40: ...ppr 15kg Dimensions of enclosure 350 x 250 x 200mm 13 7 x 9 9 x 7 9 LxHxD Environment Electromagnetic compatibility Compliant ref EN 61326 1997 EN 61010 1 1993 Flowmeter Type P Coil sine wave minimum...

Страница 41: ...ut max 50mA per output requires type AA PD PF or PM Type OR Isolated mechanic relay output max switch power 230V AC 0 5A requires type PF or PM Type OT Passive transistor output not isolated Load max...

Страница 42: ...med reasonable and will the maximum output be under 20Hz SETUP 72 impulse width is the external device able to recognize the selected pulse width and frequency Flowrate displays 0 zero while there is...

Страница 43: ...6 22 24 26 29 CONFIGURATION VARIABLES F110 A SETUP LEVEL VAR DESCRIPTION BYTES VALUE REMARKS TOTAL 32 20h unit 1 0 L 1 m3 2 kg 3 lb 4 gal 5 usgal 6 bbl 7 none 33 21h decimals 1 0 3 34 22h span 3 1 9 9...

Страница 44: ...0 default 1 calibrate 2 cal set 103 67h calibration high 20mA 1 0 default 1 calibrate 2 cal set ANALOG OUTPUT 112 70h analog output 1 0 disable 1 enable 113 71h minimum rate 3 0 9999999 unit time deci...

Страница 45: ...ytes of zero s to total will be accepted ACCUMULATED TOTAL variable number 560 230h 6 bytes Read acc total A difference between the read value and the display value as explained for Read total might a...

Страница 46: ...cally safe 34 Problem solving 42 pulse output pulse length period time 19 pulse per quantity 19 Pulse output 27 serial number 20 SETUP level 9 shelf mode 15 subfunction 10 tagnumber 20 Technical speci...

Страница 47: ...HF110AEN_v0501_04 Page 47 NOTES...

Страница 48: ...efault 6 ANALOG OUTPUT 61 output disabled 62 min flowrate 4 mA 0000000 63 max flowrate 20mA 9999999 64 cut off percentage 0 0 65 tune min 4mA 0208 66 tune max 20mA 6656 67 filter 01 off 7 PULSE OUTPUT...