Active signals:
Active signal selection may well be desired if an active signal is offered from the sensor.
Reed-switch:
The F093-P is suitable for use with Tachometers which have a reed-switch. To avoid pulse bounce
from the reed-switch, it is advised to select REED LP - low-pass filter (read par. 3.2.3.)
NAMUR-signal:
The F093-P is suitable for Tachometers with an Namur signal.
Terminal 7 can provide a 8.2V sensor supply voltage (please read section “sensor supply”).
INTERNAL
EXTERNAL
Reed - switch signal input
6
Common ground unit
SIGNAL
5
GND
shielding
REED
SWITCH
+ 3.2V DC
1M
low-pass filter
selection REED-LP
INTERNAL
EXTERNAL
Active signal input
6
Common ground unit
SIGNAL
shielding
Resistance value:
see signal selection
5
GND
7
Sensor supply 3,2 8.1, 12, 24V DC
INTERNAL
EXTERNAL
Namur signal input
Common ground unit
shielding
Namur
820 Ohm
5
GND
7
Sensor supply 8.1V DC
6
SIGNAL