4.4.
INSTALLING THE HARDWARE
4.4.1. INTRODUCTION
•
Electro static discharge does inflict irreparable damage to electronics! Before
installing or opening the unit, the installer has to discharge himself by touching a
well-grounded object.
•
This unit must be installed in accordance with the EMC guidelines (Electro Magnetic
Compatibility).
•
Do ground the aluminum casing properly as indicated, if the F093-P has been
supplied with the 115-230V AC power-supply type PM. The green / yellow wire
between the back-casing and removable terminal-block may never be removed.
Fig. 8: Grounding aluminum enclosure with option PM 115-230V AC.
FOR INSTALLATION, PAY EMPHATIC ATTENTION TO:
-
Separate cable glands with effective IP67 (NEMA4X) seals for all wires.
-
Unused cable entries: ensure that you fit IP67 (NEMA4X) plugs to maintain rating.
-
A reliable ground connection for both the sensor, and if applicable, for the metal casing. (above)
-
An effective screened cable for the input signal, and grounding of it’s screen to the “
┴
“ terminal
or at the sensor itself, whichever is appropriate to the application.