Page 28
FW-F010-A-M_v0404_01_EN.docx
Risk of damage to equipment!
Be very careful when connecting the common ground of the system to Protective Earth (PE).
Connecting the common ground to Protective Earth (PE) (especially when multiple power
supplies are connected) can cause ground loop currents that could damage the equipment.
See paragraph 4.5.2: Protective Earth (PE) connections for more information.
4.7.2
TERMINALS 5-7: FLOWMETER INPUT
The F010-A requires a (0)4-20mA flowmeter signal which will be processed 4 times a second with a
16 bit accuracy. The input is not isolated.
The screen of the signal wire can be connected to the common ground terminal. See paragraph
4.5.3.
Fig. 18: Terminal connections - Analog signal input.