0.1- 1 second …………………… 0.1 -------------------------------------------------------------------1 second
1 - 10 seconds ………………… 1 --------------------------------------------------------------------10
seconds
6 - 60 seconds ………………… 6 -------------------------------------------------------------------- 60
seconds
1 - 10 minutes ………………… 1 -------------------------------------------------------------------- 10
minutes
6 - 60 minutes ………………… 6 -------------------------------------------------------------------- 60
minutes
1 - 10 h ………………………….. 1 -------------------------------------------------------------------- 10 hours
10 - 100 h ………………………… 10 ------------------------------------------------------------------- 100 hours
NOTE : On 6-60 time range multiply the time set scale by 6.
Example – On-delay of 18 seconds is required.
a.
Set the time range knob to 6-60s position.
b.
Set the time set knob to 3. (3x6 = 18 seconds.)
3.
State indicator Un signals.
a.
No light
= The timer is in off state. (No supply on A1/A2 terminals)
b.
Blinking light
= The timer is counting/On delay.
c.
Steady light
= The timer reached the time set. (Internal relay energized)
For more information:
WEB: FLTR.com.au PHONE: (+61) 1300 62 4020 EMAIL: [email protected] SKYPE: Purple.Engineering
Содержание CSB 10
Страница 1: ...Tekleen CSB USERS MANUAL...
Страница 14: ...For more information WEB FLTR com au PHONE 61 1300 62 4020 EMAIL info FLTR com au SKYPE Purple Engineering...
Страница 20: ...For more information WEB FLTR com au PHONE 61 1300 62 4020 EMAIL info FLTR com au SKYPE Purple Engineering...
Страница 21: ...For more information WEB FLTR com au PHONE 61 1300 62 4020 EMAIL info FLTR com au SKYPE Purple Engineering...