4. Specifications
Input signal
4-20 mA
Current supply min.
3,6 mA
Current supply Max.
150 mA
Load Standard
400 ohm at 20mA
Load HART
470 ohm at 20mA
Voltage dropStandard
8 VDC at 20mA
Voltage dropHART
9.4 VDC at 20mA
Angle of rotation min
0-40
°
Angle of rotation Max
0-90
°
Air supply range
1.5 – 6 bar
Out put
0-100% of air supply pressure
Air supply quality
Free from oil, dust and moisture IEC 770,
ISA 7.0.01
Air supply effect
<0.1%FS for10% pressure change at 6 Bar
Ingress protection
IP66 / Nema 4X
Operating humidity
0-100% rh non-condensing
Air connections
1/4” NPT
Cable entry
2 x 1/2” or 2 x M20x 1,5
Terminals
Screw terminals 2,5 mm
2
(AWG 14)
Operating Temperature
-20 to +85
°
C-40 to +85
°
C (optional)
Storage temperature
-40 to +85
°
C
Air delivery capacity
7 Nm
3
/h @ 6 bar (3 bar diff pressure)
Air delivery capacity Double acting
7 Nm
3
/h @ 6 bar (3 bar diff pressure)
Air consumption Single acting
0,120 Nm
3
/h @ 6 bar
Air consumption Double acting
0,120 Nm
3
/h @ 6 bar
Cv air delivery Single acting
0,12
Cv air delivery Double acting
0,12
Cut off function
Close 0.5% Open 99.5%
Linearity
<1%
Sensitivity
<0.05%
Resolution
<0,1%
Repeatability
<0.2%
Hyst dead band
<0.5%
Temp effect
<0.1%/10K
Mounting position effect
<0,2%
CE
93/68/EEC, 2004/108/EEC, 2006/95/EEC
Approvals
II 1G Ex ia IIC T4 Ta:85
°
C
Certificate nr
Nemko 08ATEX1362X
Housing material
Die cast Aluminium
Surface treatment
Powder coating
Soft goods
Nitrile
Weight
1,5 kg
4.1 Technical data
Содержание PMV D20
Страница 1: ...Installation Operation Maintenance PMV D20 Digital Positioner ...
Страница 11: ...11 4 5 Control Drawing ...
Страница 12: ...12 4 6 Certificates ...
Страница 13: ...13 ...
Страница 14: ...14 ...
Страница 15: ...15 ...
Страница 32: ...32 12 Spare parts 12 11 16 15 19 18 17 1 21 2 14 3 5 8 7 9 4 ...