2 SPECIFICATIONS
2.1 Input Signal
Table 1: Input Signal
Positioner Alone or with Multi-Function Card
Power Supply
Two-wire, 4-20 mA
10.0 VDC plus line losses (Logix 520MD+)
6.0 VDC plus line losses (Logix 510+)
Input Signal Range
4 - 20 mA (HART)
Compliance Voltage
10.0 VDC @ 20 mA (Logix 520MD+)
6.0 VDC @ 20 mA (Logix 510+)
Effective Resistance
500 Ω @ 20 mA (Logix 520MD+) Typical
300 Ω @ 20 mA (Logix 510+) Typical
Minimum Required
Operating Current
3.8 mA
Maximum Shut-down
Current
3.6 mA
Power Interruption
Time Limit
After power has been applied for at least 10
seconds, a 60 ms power interruption will not
cause the positioner to reset.
Power-up time
Time from application of power to begin con-
trolling valve < 1.0 second.
Communications
HART protocol
2.2 Pneumatic Output
Table 2: Pneumatic Output
Output Pressure
Range
0 to 100% of air supply pressure.
Output Air Capacity
Single Acting Relay –
9.06 Nm³/h @ 1.5 bar
(5.33 SCFM @ 22 PSI)
20.8 Nm³/h @ 4.1 bar
(12.2 SCFM @ 60 PSI)
Double Acting Relay –
14.3 Nm³/h @ 1.5 bar
(8.44 SCFM @ 22 PSI)
30.6 Nm³/h @ 4.1 bar
(18.0 SCFM @ 60 PSI)
Primary Output Ports
(Port is pressurized in
energized state. Port
is exhausted upon
loss of power.)
Single Acting Relay – Port B
Double Acting Relay – Port A
2.3 Air Supply
Table 3: Air Supply
Minimum Input Pressure
1.5 Bar (22 PSI)
Maximum Input Pressure
Single Acting Relay – 6.2 Bar (90 PSI)
Double Acting Relay – 10.3 Bar (150 PSI)
Air Supply Quality
The air supply must be free from moisture,
oil and dust by conforming to the ISA 7.0.01
standard. (A dew point at least 18 degrees
Fahrenheit below ambient temperature,
particle size below five microns—one
micron recommended—and oil content not
to exceed one part per million).
Operating Humidity
0 - 100% non-condensing
Acceptable Supply Gasses
Air, sweet natural gas, nitrogen and CO2
are acceptable supply gasses. Sour natural
gas is not acceptable. For Type nA and Type
tb installation only air or inert gas may be
connected to the air supply inlet.
Air Consumption
Single Acting Relay –
0.069 Nm³/h @ 1.5 bar
(0.041 SCFM @ 22 PSI)
0.082 Nm³/h @ 4.1 bar
(0.050 SCFM @ 60 PSI)
Double Acting Relay –
0.297 Nm³/h @ 1.5 bar
(0.175 SCFM @ 22 PSI)
0.637 Nm³/h @ 4.1 bar
(0.375 SCFM @ 60 PSI)
2.4 Analog Output – Multi-Function Card
Table 4: 4 to 20 mA Analog Output Specification
NOTE:
For entity parameters, see section 3 HAZARDOUS AREA
CERTIFICATIONS.
Power Supply Range
10.0 to 40 VDC, (24 VDC Typical)
Current Signal Output
4 to 20 mA
Linearity
1.0% F.S.
Repeatability
0.25% F.S.
Hysteresis
1.0% F.S.
Operating Temperature
-52 to 85°C (-61.6 to 185°F)