Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
flowserve.com
Table 4.32 – Continued
Attribute ID Access Rule Name
Data Type
Description
Semantics of Value
20
RO
TQ_Status_4
UINT
MB_TQ_Open_
Breakout_Last
Engineering Use
21
RO
TQ_Status_5
UINT
MB_TQ_Close_
Breakout_Last
Engineering Use
22
RO
TQ_Status_6
UINT
MB_TQ_Open_
Ending_Last
Engineering Use
23
RO
TQ_Status_7
UINT
MB_TQ_Close_
Ending_Last
Engineering Use
24
RO
TQ_Status_8
UINT
MB_TQ_Close_
Peak_Last
Engineering Use
25
RO
TQ_Status_9
UINT
MB_TQ_Open_
Peak_Last
Engineering Use
26
RO
TQ_Status_10
UINT
MB_TQ_Open_
Breakout_Ref
Engineering Use
27
RO
TQ_Status_11
UINT
MB_TQ_Close_
Breakout_Ref
Engineering Use
28
RO
TQ_Status_12
UINT
MB_TQ_Open_
Ending_Ref
Engineering Use
29
RO
TQ_Status_13
UINT
MB_TQ_Close_
Ending_Ref
Engineering Use
30
RO
TQ_Status_14
UINT
MB_TQ_Close_
Peak_Ref
Engineering Use
31
RW
Travel_Limit_Low
UINT
Lower limit of the
valve position in
percent of travel
span
Range 0 – 1000
Default = 0
32
RW
Travel_Limit_Up
UINT
Upper limit of the
valve position in
percent of travel
span
Range 0 – 1000
Default = 0
33
RW
Valve_Maint_ Date
SHORT-
STRING
Date of last valve
maintenance
String length is limited
to 16 char. Default = 0
(empty)
34
RW
Valve_Serial_Num
SHORT-
STRING
Serial number of
the valve belonging
to the positioner of
electronic device
String length is limited
to 16 char. Default = 0
(empty)
35
RO
Valve_status_0
WORD
Requested relay
channel value
Default = 0
36
RO
Valve_status_1
WORD
Status Register
– Modbus Register
9
Default = 0
37
RO
Valve_status_2
WORD
Fault Register
– Modbus Register
10
Default = 0
38
RO
Valve_status_3
WORD
Digital Output
Register – Modbus
Register 11
Default = 0
39
RO
Valve_status_4
WORD
Digital Input #1
Register – Modbus
Register 12
Default = 0
40
RW
Valve_status_5
WORD
Digital Input #2
Register – Modbus
Register 13
Default = 0
Continued on next page