23
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
flowserve.com
Table 4.20 – Possible values of DI_Actuator_Alarms_Chan
Value
Definition
0x01
Local ESD Active
0x02
Remote ESD Active
0x04
Open Inhibit Active
0x08
Close Inhibit Active
0x05
Local ESD Open Inhibit Active
0x09
Local ESD Close Inhibit Active
0x06
Remote ESD Open Inhibit Active
0x0A
Remote ESD Open Inhibit Active
0x0C
Open Inhibit Close Inhibit Active
4.2.6 DI_Disc_User_Input_Chan
Table 4.21
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Discrete
Input #8
Discrete
Input #7
Discrete
Input #6
Discrete
Input #5
Discrete
Input #4
Discrete
Input #3
Discrete
Input #2
Discrete
Input #1
4.2.7 DI_Read_Disc_Output_Chan
Table 4.22
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
Relay
Discrete
Output #7
Relay
Discrete
Output6 #
Relay
Discrete
Output #5
Relay
Discrete
Output #4
Relay
Discrete
Output #3
Relay
Discrete
Output #2
Relay
Discrete
Output #1
4.2.8 DO_Position_Chan
Table 4.23
Value
Definition
0x00
Stop
0x01
Open
0x02
Close
0x03
– 0xFF
Reserved
4.2.9 DO_ESD_Chan (Read Only)
Table 4.24
Value
Definition
0x00
Disable Network ESD
0x01
Enable Network ESD
DO_ESD_Chan can’t be written directly via the DeviceNet network, it is Read-Only. The attribute
Enable_Broadcast_ESD_Ctrl defines if a device is part of the broadcast ESD control scheme from Bit-
Strobe Connection or not. The resulting DO_ESD_Chan is defined in the following table.
The MX allows the standard I/O connection to assert ESD, or the broadcast bit strobe connection to
assert ESD.