4.0 – K4 Pump Controller
4.1 Operation and Wiring
For complete details about the motor drive controller please refer to the included K4 SERIES Operating
Instructions booklet.
IMPORTANT: Make sure the Mains voltage jumper is in the correct location for the supplied
voltage. See the K4 drive operating instructions booklet for details.
Shown here are program settings specific to the operation with the 2001H Peristaltic Pump.
4.2 Programming
The programming differs from the factory defaults shown in the SM Vector Operating Instruction booklet only in
relation to the following parameters:
KB Default Program Settings
0.04 = 0000 GFCI disabled, enable if power pump through GFCI mains circuit (some additional noise from the drive is
normal).
1.00 = 0001 Remote Start/Stop contacts enable (CHANGE TO 0000 to use 4-20 with manual start/stop)
1.05 = 0003 Power fail auto restart
2.00 = 0003 Freq Control Analog 2 (4-20mA)
2.01 = 0001 Speed change w/o pressing enter
2.02 = 0002 Enable external Local/Remote switching
3.00 = 0005 Stored Set Frequency (5hz)
3.02 = 0100 Upper Frequency Limit
4.00 = 0000 Display in user defined units (Hz)
5.00 = 0000 Enable Run Relay N.O.
7.03 = 0010 Remote Start/Stop - N.O. Start
7.04 = 0000 External Local/Remote Select OFF (13 for remote auto select)
7.06 = 0008 External Fault input select
8.00 = 0001 NC Fault Relay
8.01 = 0009 Enable Status Output
9.07 = 0020 4-20mA Input
8.09* = 0002 When speed feedback 4-20ma output is connected
NOTES:
*8.09 = 0000 to avoid fault when 4-20mA Output is disconnected when not using 4-20mA output
Keypad speed can only be changed in local mode
For manual speed with remote start/stop set 2.00 to 0000
For remote (4-20ma) speed with manual (keypad) start/stop set 1.00 to 0000
Large hose pumps - Boost Value 3.11 default 7, up to 12 or higher
6.05 = 1010 reset to Flomotion Defaults
4.3 To display speed in GPH:
Fill a calibration cylinder (best to use water, not chemical for testing and calibration)
Run the pump at full speed and time the drawdown for 30 sec. (from zero level in cylinder).
Note the level in the calibration cylinder when 30 seconds has elapsed. That will be your full scale pumped flow
rate.
Set menu 4.00 to 0001 (custom units).
Set menu 4.01 to the GPH of the pump at full speed.