![FLOWmetrix SAFMAG ACP HI-PULS METER Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/flowmetrix/safmag-acp-hi-puls-meter/safmag-acp-hi-puls-meter_installation-and-operation-instructions_2308323016.webp)
15
User’s Guide 2018
MENU-1 Flow Data
Menu-1
M-cont S-enter
Press
SAVE
to enter or
MENU
to continue
M1_1 rate units
l/s
Press
▲
repeatedly until desired units are displayed and
MENU
to continue
M1_2 max flow
100 l/s
Enter the maximum forward flow rate at which to output 20mA Fwd current
Press
► repeatedly until cursor is under digit to be edited
Press ▲ repeatedly until desired value is displayed and
MENU
to continue
M1_3 flow alarm
20 l/s
Enter the flow rate at which the flow alarm must operate
Press
► repeatedly until cursor is under digit to be edited
Press ▲ repeatedly until desired value is displayed and
MENU
to continue
M1 -4 tot units
m3
Select the unit in which you wish to totalise
Press ▲ to select option required and MENU to continue
M1_5 clr total?
Yes/No
Select to clear or save the existing flow total
Press ▲ to select option required and
MENU
to continue
M1_6 damping
Level 2
level 0, level 1, level 2, level 3, level 4, level 5
damping settings are available
Press ▲ to select the required value and
M
to continue