Flowmetrics 913 DRT Скачать руководство пользователя страница 3

1

    DESCRIPTION & SPECIFICATIONS

DESCRIPTION:
The  913 DRT (Dual Rate Totalizer) is a dual 5 digit Ratemeter 6
digit Totalizer in  a 1/8 DIN package. User selects 1 of 6 displays to
show A,B or C rate and A,B or C total. Inputs A and B have
separate scaling to read in engineering units.
A 4-20mA (0-20mA) output of the C rate or total is optional.
The user can press the VIEW button to see 6 separate items
 total A, total B, total C, rate A, rate B, rate C. Negative values are
displayed with a negative symbol ( -

 12345 

). For the C value, the

user can choose from the following combination of A&B inputs:
TOTAL; with a choice of A+B or A-B; RATIO with choice of
A

÷

B(x100) to show percent of A to B quantity or A

÷

[A+B(x100)] to

show percent of A to total quantity.
Two independent presets are standard. User selects whether out-
put A is activated by total or rate value of input A or selected C.
Output B can be activated by total or rate value of input B or
selected C. Outputs activated by A or B total can be set to latch or
autorecycle with an adjustable output duration from 00.1 to 99.9
sec. For rate, ratio, or C total outputs pull in when value is equal or
above the preset and drop out when value is below the preset
minus the selected 0 to 999 hysteresis.

SPECIFICATIONS:

DISPLAY
6 digit, 0.55" High LED

INPUT POWER:

110 VAC 

±

 15% or 12 to 15 VDC

220 VAC 

±

 15% or 12 to 15 VDC

24 VAC 

±

 15% or 12 to 15 VDC

CURRENT:
250 mA DC max. or 6.5 VA  AC

OUTPUT POWER  (AC powered units only)
+12 VDC @ 50 mA, unregulated -10 + 50%

TEMPERATURE:
Operating:

+32

°

F (0

°

C) to +130 F (+54

°

C)

Storage:

-40 F (-40

°

C) to +200

°

F (93

°

C)

MEMORY
EEPROM stores data for 10 years if power is lost.

INPUTS:
3:

High Impedance DC pulse input  4-30 VDC (high), Open or 0-
1 VDC (low),10 K

 imp. 10 kHz max. speed. Accepts simul-

taneous inputs.  May be used with KEP 711 series  or PD & D
series sensors.

3M:

Mag. Input, Input A only, accepts 30mV input (50 V max. P/P)
signals 10 K

 imp. 5 kHz max. (Input B, 4-30V)

3MB: Mag. Input, Inputs A & B, accepts 30mV input (50 V max. P/

P)  signals 10 K

 imp. 5 kHz max.

NOTE: The Mag. inputs have filtering as follows:  up to 300hz

@30mV, 5KHz @ .25V to 50V max.

RESET:

Front Panel:

Resets displayed value and control output

Remote:

4-30 VDC  negative  edge resets all counters,
"A" counter or "B" counter (user selectable).

K FACTOR/SCALING
The  913 DRT has two separate K-Factors that are used to convert
the input pulses to engineering units.  The 5 digit K-Factor dividers,
with decimal keyed into any position, allow easy direct entry of any
K-Factor from 0.0001 to 99999.  Separate factors may be entered
for the 2 separate input channels.

CONTROL OUTPUTS:
Relays:

2 each N.O. Relay; 10 Amps120/240 VAC or 28 VDC.
(N.C. relay contacts and NPN transistor output
available with solder jumpers.  Transistor output is
internally pulled up to 10 VDC through relay coil, sinks
from 10 VDC to .5 V @ 100 mA)

Analog Output:

An optional 4-20mA (0-20mA) output is available for
the  913 DRT.  The output can be programmed
to track rate or total of the C display.  This feature is available
by adding suffix A to the part number.  Connections are
via a 2 terminal pluggable screw connector.
Programming is accomplished by using the front panel
in conjunction with rear dip switches.
Accuracy: 50uA worst case.
Compliance Voltage: 3 to 30 VDC non inductive.

RS232/RS422SERIAL INTERFACE
If the serial interface option is supplied, up to 99 units can be linked
together. (The terminal addressing the unit must be capable of
driving all loads in the loop.)  Unit status and new set points can be
communicated by serial communication. Mode changes, however,
must always be made on the front panel. Data is transmitted at
selected baud rates using standard seven bit ASCII characters and
parity with two additional bits of “Start” and “Stop” to make up the
standard ten bit character.
Data is received and transmitted over standard EIA RS232 or
RS422 levels. Each 10 bit character is made up of a start bit, 7 bit
ASCII code, parity bit and stop bit. Unit number, baud rate and
parity are entered in the “Program Setting” set up mode and remain
in memory even if power is off.
Note that the input impedance of RS232 is 3K or 7K Ohm worst
case. The terminal addressing the unit must be capable of driving
all loads in the loop. RS422 input impedance is much higher and
there is usually no problem driving 25 units. Unit serial transmit line
remains in a high impedance “OFF” state until addressed.

PRESETS
Two control outputs are provided.  To set relay values, press “menu”
button until “Relay” appears on  the display, the A and B outputs can
be assigned to the A,B or C displays.  A 5 digit value can be entered
for both presets and the decimal point location is the same as the
counter.  The outputs can be set to energize from 0.1 to 99.9
seconds or latch (0.0). If a value other than 0.0 is entered, the
counters will auto reset at the preset (for A&B counters).

Содержание 913 DRT

Страница 1: ...913 DRT DUAL RATE TOTALIZER INSTALLATION OPERATING INSTRUCTIONS 99827 08 27 01 ...

Страница 2: ...PROGRAMMING FLOW CHART 7 PROGRAM CODES DESCRIPTIONS 8 913 DRT TERMINATIONS 10 CALCULATING SCALE FACTORS 11 913 DRT PROGRAMMING PROCEDURE 12 SETTING SCALING FACTORS 12 SETTING THE COUNTER 13 SETTING THE RATE 14 SETTING THE LOCK CODE LOCKING THE UNIT 15 SETTING THE RELAYS PRESETS 16 OUTPUT WIRING 18 ANALOG OUTPUT OPTION 19 RS232 RS422 SERIAL COMMUNICATIONS 20 TROUBLESHOOTING GUIDE 23 WARRANTY 24 TAB...

Страница 3: ...convert the input pulses to engineering units The 5 digit K Factor dividers with decimal keyed into any position allow easy direct entry of any K Factor from 0 0001 to 99999 Separate factors may be entered for the 2 separate input channels CONTROL OUTPUTS Relays 2 each N O Relay 10 Amps120 240 VAC or 28 VDC N C relay contacts and NPN transistor output available with solder jumpers Transistor outpu...

Страница 4: ...ed out or the presets can remain accessible RATEMETER Accurate to 4 1 2 digits 1 display digit The ratemeter uses 1 tau with 8 digit math can sample from 2 to 24 seconds maximum and auto range up to 5 digits of significant information In the RPS mode the ratemeter displays in units per second and in the scale mode units per hour or per minute The unit will display the rate of the A B Inputs COUNTE...

Страница 5: ...ounted is less than 125 of an inch thick the possibility exists that there will be some flexing Should this flexing occur the resulting deformation of the panel could cause a loss of the water tight seal In case this should occur the use of silicone or other sealant would be recommended This product is designed to the NEMA 4 rated However the fact that we are unable to control either the location ...

Страница 6: ...ine noise The noise is carried on the input and D C ground lines Make sure the input wires are never run into the unit in a bundle with power input lines Also keep these input lines isolated from inductive lines from devices drawing heavy loads If there is a possibility of electrical noise we recommend using shielded cable with the shield being hooked to the D C ground terminal on the instrument a...

Страница 7: ...Ohms to ground The unit can be programmed from the front panel for slow switch closure inputs up to 40Hz select Lo CPS or solid state switches select hi CPS up to 9 99KHz No rear terminal jumpers are required Use PNP sourcing type pulsers 1 COMMON 2 N O N C NPN 3 COMMON 4 N O N C NPN 5 A INPUT 6 B INPUT 7 12 V OUTPUT DC INPUT 8 DC GROUND 9 RESET INPUT 10 NOT USED 11 AC INPUT 12 AC INPUT COUNT POWE...

Страница 8: ...O J1 C J2 O J3 C InputB J4 O J5 C J6 O J4 C J5 O J6 C The unit must be removed from the case to access jumpers C F all other jumpers can be accessed by removing the plastic extender NOTE All three pads at jumpers 2 and 4 are connected J4 J5 J6 J3 J1 J2 CR1 R3 C8 R7 R5 R4 U1 CR2 REV 20229 CR6 CR3 U3 P1 R10 R6 C6 C7 CR4 CR5 C4 R2 R1 C3 C5 U2 U4 U6 U5 R8 R9 C1 C2 C9 B FUNCTION A RELAY N C OUTPUT B RE...

Страница 9: ...tio E PRGM nor figur dly code lc all lc prg RST ENTER a tot a rate RST ENTER RUN MODE E PRGM E PRGM E PRGM E PRGM E PRGM E PRGM DP F b RST ENTER RST ENTER RST ENTER RST ENTER RST ENTER RST ENTER RST ENTER DP loc RST ENTER a addb asub b E PRGM rst al rst 1 E PRGM RST ENTER hi cps lo cps E PRGM rps scale E PRGM z 60 z 3600 E PRGM RST ENTER RST ENTER RST ENTER a b a a b E PRGM RST ENTER RST ENTER RST...

Страница 10: ...pulses from the A Input are added to the number of scaled pulses from the B Input a b A DIVIDED BY B The number of scaled pulses of input A are divided by the number of scaled pulses of input B X 100 to give the percent ratio of A B a a b A DIVIDED BY A PLUS B The number of scaled pulses of input A divided by A plus the number of scaled pulses of input B X 100 to give the percent ratio of A A B RS...

Страница 11: ...is is selected the user has a choice of having Preset A follow the A tot a or C tot c display tot a RELAY A FOR A TOTALIZER If selected the A output is activated by A total and user can select auto recycle with duration of 00 1 to 99 9 sec or latched till reset if 00 0 is programmed tot c RELAY A FOR C TOTALIZER If selected the A output is activated when C total is equal or greater then preset A a...

Страница 12: ... is programmed tot c RELAY B FOR C TOTALIZER If selected the B output is activated when C total is equal or greater then preset B and drops out when C total goes below preset B by selected 0 99 9 hysteresis b RATE RELAY B FOR RATE When this is selected output B will activate when the Rate of either display B or display C user selectable equals or exceeds preset B The relay will drop out when the s...

Страница 13: ...her so a sensor is placed at the roller sensing seven pulse per revolution of the shaft which equals 3 bottles per revolution To calculate the scale factor 7 ppr 3 bottles 2 3333 scale divider Set rate per second minute or hour as desired FLOW IN LITERS A flow meter is generating 52 6 pulses per gallon The desired readout is in liters Since there are 3 785 liters per gallon divide 52 6 by 3 785 to...

Страница 14: ... A To change press the arrow key under the digit s Press ENTER to enter the displayed value This sets the decimal for factor B Press the arrow key under the digit where the decimal is desired To clear the decimal press the arrow key fur thest to the right PRGM This is the scaling factor for input B To change press the arrow key under the digit s Press ENTER to enter the displayed value DISPLAY fac...

Страница 15: ...key to enter the displayed choice This section will only appear if RATIO is selected Choose A B or A A B Press the ENTER key to enter the displayed choice Press the PRGM key to choose RESETALL resettingA B Cdisplays or RESET 1 resetting a choice of either A or B display Press the ENTER key to enter the displayed choice Press the PRGM key to choose RESET A or RESET B Press the ENTER key to enter th...

Страница 16: ...arrow keys under the de sired digits to change Press ENTER to enter displayed value This sets the number of significant figures to be displayed Press the arrow key un der the digit to change Press ENTER to enter displayed value This sets the delay time 2 to 24 sec that the unit will look for valid input data be fore the display falls to 0 Press the arrow key under the digits to change Press EN TER...

Страница 17: ...isplay will show the existing lock code To change the code press the key under each digit to be changed Press ENTER to enter displayed value When in the run mode press LOCK After CODE goes out key in the lock code see programming step 4 by pressing the keys under the digits to be changed Press the ENTER key to enter the displayed code After the code is entered the unit will display LOC unit is loc...

Страница 18: ... tot is se lected Press the PRG button to choose tot a or tot c Press the ENTER key to enter the displayed choice Set relay duration 1 to 99 9 sec Counter autoresets and relay is energized for selected time If 00 0 is selected counter does not autoreset Output is active if counter is equal or above preset This is the hysteresis setpoint for relay A 00 0 to 99 9 This section will only appear if tot...

Страница 19: ...e b or rate c hy SETTING THE PRESETS Press the PRGM key to choose B TOT B relay assigned to total or B RATE B relay assigned to rate Press enter when the desired choice is displayed This section will only appear if b tot is se lected Press the PRG button to choose tot b or tot c Press the ENTER key to enter the displayed choice Follow same procedures as A This is the hysteresis setpoint for relay ...

Страница 20: ...NPUT 6 B INPUT 7 12VDC OUT DC IN 8 DC GROUND 9 RESET INPUT 10 NOT USED 11 A C INPUT 12 A C INPUT RELAYS A B 13 V 14 I SINK ANALOG OUTPUT ON CAL 0 20mA COUNT SET OFF RUN 4 20mA RATE RUN 1 2 3 4 ON SWITCH D08P Prox Sensor BLK BRN BLU ALARMS The relays can be used to trigger alarms which warn the operator that a batch is complete or the rate has exceeded a set speed The outputs are programmable to be...

Страница 21: ...buttons A through E to step to desired value and press ENTER Return switch 1 to OFF down position PRE A and PRE B buttons now function to view or change relay trip values SWITCH 2 Select Count or Rate SW2 OFF down Analog output follows C rate SW2 ON up Analog output follows C count SWITCH 3 Select 4 20mA or 0 20mA SW3 OFF down Selects 4 20mA output range SW3 ON up Selects 0 20mA output range SWITC...

Страница 22: ... if the transmission is correct When setting the parity you may select ODD parity bit is logic 0 if total number of logic 1 s in the first seven data bits is odd EVEN parity bit is logic 0 if total number of logic 1 s in the first seven data bits is even MARK parity bit is always logic 1 High Mark or SPACE parity bit is always logic 0 Low Space If a MARK parity is chosen it will appear that two st...

Страница 23: ... TheinputimpedanceofRS232is3KΩto7KΩworstcase The terminal addressing the unit must be capable of driving all loads in the loop The input impedance of RS422 is much higher and there should be no problem driving as many as 99 units The transmit line remains in a high impedance off state until addressed Only one unit is to be on line at a time More than one unit on line could damage the unit or destr...

Страница 24: ...A PIN 2 GROUND PIN 5 RS 422 TRANSMIT B PIN 7 STROBE PIN 6 12V PIN 7 BOTTOM BOARD A RST B C D E ENTER LOCK PRE A PRE B VIEW PRGM TRANSMIT PIN 2 GROUND PIN 5 RS 232 STROBE PIN 6 12V PIN 7 BOTTOM BOARD RS232 RS422 WIRING 1 2 3 4 5 6 7 8 9 RS 232 1 INITIALIZE 2 TRANSMIT 3 RECEIVE 4 N C 5 GROUND 6 STROBE 7 N C 8 N C 9 N C RS 422 1 INITIALIZE 2 TRANSMIT A 3 RECEIVE A 4 N C 5 GROUND 6 STROBE 7 TRANSMIT B...

Страница 25: ...i e count instead of rate 1 Relay duration is set at a value other than 00 0 This causes the counter to auto reset at the preset 1 Recheck power wiring 1 Use a different power supply or install a surge suppressor 1 Recheck input wiring 2 Recheck scale factors and factor calculations 3 Replace transmitting device 4 Recheck debounce filtering selection hi cps or lo cps 5 To confirm set scale factors...

Страница 26: ...rranty is limited to repair or replacement of the defective unit at the option of the manufacturer This warranty is void if the product has been altered misused dismantled or otherwise abused ALL OTHER WARRANTIES EXPRESSED OR IMPLIED ARE EXCLUDED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ...

Отзывы: