M81

 

The built-in batch controller

 

Set the flow batch value(dose)

 

The internal output of the batch controller can be directed either to the OCT or the

 

RELAY output circuits.

 

M81 and M80 should be used together to configure the batch controller.

 

Note: Because the measuring period is 500mS, the flow for every dos should be 
keeping at 60 second long to get a 1% dose accuracy

 

M82

 

View the daily, monthly and yearly flow totalizer and thermal energy totalizer value.

 

The totalizer values and errors for the last 64 days, 32 last 32 months and last 2 years 
are

 

stored in the RAM memory, To view them, use the ‘ENT’ and ‘UP’ ‘Down’ keys.

 

M83

 

Automatic Amending Function for automatic offline compensation.

 

Select ‘YES’ to enable this function, select ‘NO’ to disable it.

 

When

 

the function is enabled, The flow meter will estimate the average flow 

uncounted

 

(or ‘lost’) during the offline session and add the result to the totalizer.

 

The estimation of the uncounted flow is made by computing the product of the offline

 

time period and the average flow rate, which is the average of the flow rate before 
going

 

offline and the one after going on line.

 

M84

 

Set the thermal energy unit:

 

0. GJ 1. KC 2.KWh 3. BTU

 

M85

 

Select temperature sources

 

0. from T1,T2 (factory default)

 

1. from AI3,AI4

 

M86

 

Select the Specific Heat Value.

 

Factory default is ‘GB’. Under this setting, the flow meter will calculate the enthalpy 
of water based on the international standard.

 

If the fluid is other than water, you should select option ‘1. Fixed Specific Heat’,

 

and 

enter the specific heat value of the fluid.

 

M87 

 

Turn on or turn o ffthe Energy totalizer.

 

M88

 

Select thermal energy totalizer multiplying factor.

 

Factory default is ‘1’.

 

M89

 

1. Display the temperature difference

 

2. Window for entering the lowest  temperature difference.

 

*M90

 

Display signal strengths S (one for upstream and one for downstream), and signal 
quality

 

Q value.

 

Signal strength is presented by 00.0 to 99.9, the bigger the value, the bigger the signal

 

strength will be, and more reliable readings will be made.

 

Q value is presented by 00 to 99, the bigger the better. It should at least be great than 
50 for normal operations.

 

*M91

 

Displays the Time Ratio between the Measured Total Transit Time and the Calculated

 

time. If the pipe parameters are entered correctly and the transducers are properly

 

installed, the ratio value should be in the range of 100±3%. Otherwise the entered

 

parameters and the transducer installation should be checked.

 

M92

 

Displays the estimated fluid sound velocity. If this

 

value has an obvious difference 

with the actual fluid sound speed, pipe parameters entered and the transducer 
installation should be checked again.

 

M93 

 

Displays total transit time and delta time(transit time difference)

 

M94

 

Displays the Reynolds number

 

and the pipe factor used by the flow rate measurement

 

program. Pipe factor is calculated based on the ratio of the line-average velocity and 
the cross

-section average velocity.

 

M95 

 

(1)

 

Display the positive and negative energy totalizers

 

(2)

 

Upon entering this window, the circular display function will be started 
automatically. The following windows will be displayed one by one, 
each window will stay for 8 second : 
M95>>M00>>M01>>M02>>M02>>M03>>M04>>M05>>M06>>M0
7>>M08>>M90>>M91>>M92>>M93>>M94>>M95. 

 

This function allows the user to visit all the impormation without any 
manual action

 

To stop this function, simply press a key. Or switch to a window other 
than 95

Содержание WUF100 CF Series

Страница 1: ......

Страница 2: ...on of Ultrasonic ow meter Ultrasonic Flowmeter Converter Transducer Bracket 1 2 Types of Converters Items Separated Mount Wall mount WUF100 CF Fix Mount WUF100 IR 1 3 Types of Flow Temperature Transdu...

Страница 3: ...3 Measuring Diagrams 3 1 Separated Mounting Clamp On Inline 3 2 Fixed Mounting Clamp On Inline 4 Converter Installation and Wiring Diagram 4 1 Separated Mounting WUF100 CF Dimention...

Страница 4: ...rail mounting by using rail xing clamps DIN rail mounting by using PCB bracket Converter of WUF100 CF can be installed on the wall or in distribution box and explosion proof box Converter of WUF100 CF...

Страница 5: ...WUF 100 CF Wiring Diagram Thickness 75mm Thickness 165mm Wall moun ng Fix the onverter Explosion proof grade D BT5 with 4 6 expansion bolts Fix the converter with 4 8 expansion bolts 4 2 Fix mounting...

Страница 6: ...100 IR Wiring Diagram Open the back cover and complete the wiring To avoid leaking please tighten the water joint and screws of the back cover after wiring Be sure not to open the front cover 5 Displ...

Страница 7: ...nu windows that are numbered by M00 M01 M02 M99 Method to enter Menu Press MENU rst and follow the two digit number keys Take M35 as an example the correct key sequence is MENU 3 5 To move between the...

Страница 8: ...e ash memory so that these parameters will be solidi ed and will be loaded as the default parameters every time when power is turned on M27 To save the installation point parameter M28 Maintain the la...

Страница 9: ...ontrol 1 If Send to RS485 is selected all the data produced by the data logger will be transmitted out through the RS 232 RS485 interface 2 If To the internal serial BUS is selected the data will be t...

Страница 10: ...oper input source the OCT circuit will close when the trigger event occurs M79 Relay or OCT2 setup By selecting a proper input source the RELAY will close when the trigger event occurs M80 Window for...

Страница 11: ...l energy totalizer multiplying factor Factory default is 1 M89 1 Display the temperature di erence 2 Window for entering the lowest temperature di erence M90 Display signal strengths S one for upstrea...

Страница 12: ...convenience of eld working All the values are in single accuracy The calculator can be used while the ow meter is conducting ow measurement Water density and PT100 temperature can also be found in th...

Страница 13: ...d to select the pipe material and then press ENT key 4 Press key to enter M16 window press ENT key to enter the option selection mode Use keys and to select the liner material and then press ENT key S...

Страница 14: ...ultrasonic signal transmission and would decrease the inner diameter as well As a result the measurement accuracy can not be guaranteed Please try to avoid choosing the installation point with inside...

Страница 15: ...verter Instrument well When measuring underground pipes or need to protect the measuring points an instrument well is required To ensure the enough installation space the sizes of instrument well shou...

Страница 16: ...pipe axis and equal to the distance shown in the converter As shown A B are the two installation points Z method 1 Firstly according to the installation distance shown in converter positioning two poi...

Страница 17: ...ase verify the parameters of pipeline and liquid To ensure the installation accuracy 1 Installation procedure Select an installation method Input the measuring parameters Positioning installation poin...

Страница 18: ...space or the transducers can be only installed onthe top of pipeline parallel insertion transducer will be a good choice Pipe size 300 Positioning of parallel insertion transducer need to meet the 3 f...

Страница 19: ...correct point If not need to positioning point B and C again As shown A B are the two installation points 4 Fix ball valve base Welding Fix For carbon steel pipes the ball valve base can be welded dir...

Страница 20: ...ng the installation of ball valve and base insert the open hole tool into ball valve and lock it Then open the ball valve start drilling from slow to fast Close ball valve after drilling See more deta...

Страница 21: ...value is between 97 103 the installation is correct If not need to re adjust the insertion depth and transmit direction until meet the requirement 7 Check installation Please see details in Chapter 7...

Страница 22: ...ent Signal strength and Q value Installation Judgement 60 Can not work 60 75 Bad 75 80 Good 80 Excellent 2 Check transmission time ratio M91 is used for displaying transmission time ratio It is a perc...

Страница 23: ...Page 22 Also Provide connectors level sensor level switch electromagnetic ow meter coriolis ow meter re pump test meter...

Отзывы: