FlowLine Switch-Pro LC4 Series Скачать руководство пользователя страница 9

MN301520 Rev A1 

9  

|

 

Getting Started

 

Step Four 

  

 

GUIDE TO CONTROLS: 

 

Below is a listing and the location of the different components for the controller: 

 

1. Power 

indicator: 

This green LED lights when AC power is ON.

 

2. 

Relay indicator: 

This red LED will light whenever the controller energizes the relay, in response to the 

proper condition at the sensor input(s) and after the time delay. 

3.  AC Power terminals: 

Connection of 120 VAC power to the controller.  The setting may be changed to 240 

VAC if desired.  This requires changing internal jumpers; this is covered in the Installation section of the 
manual. Polarity (neutral and hot) does not matter.

 

4.  Relay terminals (NC, C, NO): 

Connect the device you wish to control (pump, alarm etc.) to these 

terminals: supply to the COM terminal, and the device to the NO or NC terminal as required.  The switched 
device should be a non-inductive load of not more than 10 amps; for reactive loads the current must be 
derated or protection circuits used. When the red LED is ON and the relay is in the energized state, the NO 
terminal will be closed and the NC terminal will be open.

 

5. Time 

delay: 

Use potentiometer to set delay from 0.15 to 60 seconds.  Delay occurs during switch make 

and switch break.

 

6.  Input indicators:  

Use these LEDs for indicating WET or DRY status of switch.  When switch is WET, LED 

will be Amber.  When switch is DRY, LED will either be Green for powered switches or OFF for reed 
switches.  

Note: Reed switches may be reversed for WET/OFF, DRY/Amber LED indication. 

7.  Invert switch:  

This switch reverses the logic of the relay control in response to the switch(es): conditions 

that used to energize the relay will now de-energize the relay and vice versa.

 

8.  Latch switch (LC41 and LC42 series only):  

This switch determines how the relay will be energized in 

response to the two sensor inputs.  When LATCH is OFF, the relay responds to sensor Input A only; when 
LATCH is ON, the relay will energize or de-energize only when both switches (A and B) are in the same 
condition (both wet or both dry).  The relay will remain latched until both switches change conditions.

 

9.

 

Input terminals: 

Connect the switch wires to these terminals:  

Note the polarity:

 

(+) is a 13.5 VDC, 30 

mA power supply (connected to the red wire of a FLOWLINE powered level switch), and (-) is the return 
path from the sensor (connected to the black wire of a FLOWLINE powered level switch).  

With powered 

level switches, if the wires are reversed, the sensor will not work.  With reed switches, wire polarity does 
not matter.

 

 

 

 

 

Содержание Switch-Pro LC4 Series

Страница 1: ...Flowline Inc 10500 Humbolt Street Los Alamitos CA 90720 p 562 598 3015 f 562 431 8507 w flowline com MN301520 Rev A1 LC40 LC41 and LC42 Series Manual Switch Pro Remote Level Controller ...

Страница 2: ...tings FEATURES Fail Safe relay control of pumps valves or alarms with a 0 15 to 60 second delay Polypropylene enclosure can be DIN rail mounted or back panel mounted Easy setup with LED indicators for sensor s power and relay status Invert switch changes relay state from NO to NC without rewiring AC powered TABLE OF CONTENTS Specifications Dimensions 3 Specifications 3 Dimensions 3 Safety Precauti...

Страница 3: ...on Sensor relay power status Contact type 1 SPDT Relay LC41 Series only 1 SPDT Relay Latched LC42 Series only 2 SPDT Relays only 1 Latched Contact rating 250 VAC 10A Contact output Selectable NO or NC Contact latch Select On Off LC41 LC42 only Contact delay 0 15 to 60 seconds Electronics temp F 40 to 158 C 40 to 70 Enclosure type 35mm DIN EN 50 022 Enclosure material PP U L 94 VO Fail safety Power...

Страница 4: ... series faceplate 1 sensor input 1 relay output LC41 series faceplate 2 sensor inputs 1 relay output The relay included is a latching relay LC42 series faceplate 3 sensor input 2 relay outputs One relay is latching and the other is a single input relay INTERNAL CONTROLLER LOGIC ...

Страница 5: ...esentative for further information Install In a Dry Location The controller housing is not designed to be immersed When installed properly it should be mounted in such a way that it does not normally come into contact with liquid Refer to an industry reference to ensure that compounds that may splash onto the controller housing will not damage it Such damage is not covered by the warranty Relay Co...

Страница 6: ...High Level Low Level or Pump Protection LC41 1001 E 240 VAC LC42 1001 120 VAC 3 1 1 Alarm Relay 1 High Level Low Level or Pump Protection Latching Relay 2 Automatic Fill Automatic Empty High Level Low Level or Pump Protection LC42 1001 E 240 VAC Owner s Manual 240 VAC OPTION When ordering any 240 VAC version of the LC40 series the controller will arrive configured for 240 VAC operation 240 VAC ver...

Страница 7: ...out of liquid Low Alarm Invert is ON Relay will energize when the switch becomes Dry out of liquid and will de energize when the switch becomes Wet Single Input Relays may be used with almost any kind of sensor signal current sensing or contact closure The relay is a single pole double throw type the controlled device can be connected to either the normally open or normally closed side of the rela...

Страница 8: ...dry Automatic Fill Latch is ON Invert is ON Relay will energize when level is below the bottom switch both switches are dry Relay will de energize when level reaches high switch both switches are wet The Dual Input Automatic Fill Empty Relay may be used with almost any kind of sensor signal current sensing or contact closure The relay is a single pole double throw type the controlled device can be...

Страница 9: ...om 0 15 to 60 seconds Delay occurs during switch make and switch break 6 Input indicators Use these LEDs for indicating WET or DRY status of switch When switch is WET LED will be Amber When switch is DRY LED will either be Green for powered switches or OFF for reed switches Note Reed switches may be reversed for WET OFF DRY Amber LED indication 7 Invert switch This switch reverses the logic of the...

Страница 10: ... indicate wiring for your switch Note the Shield wire will be used only for long cable runs or where excessive electrical noise is present LV10 series can be wired using the White and Black wires for NO operations or the Red and Black wires for NC operations LED INDICATION Use LED s located above the input terminals to indicate whether the switch is in a wet or dry state Powered level switches o G...

Страница 11: ...rve the Power Supply label which identifies the power requirement 120 or 240 VAC and the terminal wiring Note Polarity does not matter with the AC input terminal CHANGING FROM 120 TO 240 VAC 1 Remove the back panel of the controller and gently slide the printed circuit board from the housing Use caution when removing the PCB 2 Located jumpers JWA JWB and JWC on the PCB 3 To change to 240 VAC remov...

Страница 12: ...ontroller may be mounted by either a back panel using two screws through mounting holes located at the corners of the controller or by snapping the controller on 35 mm DIN Rail Note Always install the controller in a location where it does not come into contact with liquid ...

Страница 13: ...e alarm to the NC side of the relay terminal of the controller If power is lost the relay will be de energized and the alarm will sound if there is still power to the alarm circuit itself Note If power is accidentally cut to the controller the level switch s ability to notify the operator of a low level alarm could be lost To prevent this the alarm circuit should have a non interruptible power sup...

Страница 14: ...NO side of the relay When the relay is energized the valve will open and fill the tank In this case Invert should be ON The relay indicator will correspond directly to the open close status of the valve Determining the settings of LATCH and INVERT This is the way the system must operate When both the high and low sensors are dry the valve will open relay energized starting to fill the tank When th...

Страница 15: ...The relay indicator will correspond directly to the on off status of the pump Note If the pump motor load exceeds the rating of the controller s relay a stepper relay of higher capacity must be used as part of the system design LEAK DETECTION A leak detection switch is installed either inside the interstitial space of the tank or through the outer wall The switch will remain wet 99 99 of the time ...

Страница 16: ...us of the level switches and compare that status against the Input LEDs If the level switches state Wet or Dry corresponds to the Input LEDs proceed to the relay If the level switches state Wet or Dry does not correspond to the input LEDs then check the functionality of the level switches RELAY LOGIC INDIEPENDENT RELAY Relay will act directly based upon the status of the level switch When the leve...

Страница 17: ... when power is supplied to the controller 2 Input LED s The input LED s on the controller will be Amber when the switch es is are wet and Green or OFF when the switch es is are dry If the LED s are not switching the input LED test the level switch 3 Alarm Relay 1 input When the input LED turn OFF and ON the relay LED will also switch With invert OFF the relay LED will be ON when the input LED is O...

Страница 18: ...wiring to sensor each sensor Second check status of Relay LED If incorrect flip the Invert switch to change the relay state Controller is powered but nothing happens First check the Power LED to make sure it is Green If not check the wiring power and make sure the terminal is seated correctly over the 6 pins TESTING RELAYS Normally Open NO Wiring The relay contacts are true dry contacts with no vo...

Страница 19: ...MN301520 Rev A1 19 This Page Left Intentionally Blank ...

Страница 20: ...ocedures outlined above 2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service personnel authorized by Flowline have attempted to repair 5 have been involved in accidents or natural disasters or 6 are damaged during return shipment to Flowline Flowline reserves the right to unilateral...

Отзывы: