FlowLine LC30-1001 Скачать руководство пользователя страница 4

Step Four

Step Five

GUIDE TO CONTROLS

INSTALLATION

1. Power indicator:

This green LED lights when AC power is ON.  

2. Relay indicator:

This red LED will light whenever the con-

troller energizes the relay, in response to the proper condition at
the sensor input(s) and after the time delay.  

3. AC Power terminals:

Connection of 120 VAC power to the

controller. The setting may be changed to 240 VAC if desired.
This requires changing internal jumpers; this is covered in the
Installation section of the manual. Polarity (neutral and hot) does
not matter.

4. Relay terminals (NC, C, NO):

Connect the device you wish to

control (pump, alarm etc.) to these terminals: supply to the COM
terminal, and the device to the NO or NC terminal as required.
The switched device should be a noninductive load of not more
than 10 amps; for reactive loads the current must be derated or
protection circuits used. When the red LED is ON and the relay is
in the energized state, the NO terminal will be closed and the NC
terminal will be open.

5. Invert switch:

This DIP switch reverses the logic of the relay

control in response to the sensor(s): conditions that used to ener-
gize the relay will make it turn off and vice versa.

6. Time Delay:

After the input(s) change(s) state, this control sets

a delay from 0.15 to 60 seconds before the relay will respond. 

7. Input 1:

This amber LED will light immediately whenever the

appropriate sensor attached to the terminals detects liquid, and
will turn off when it is dry.

8. Input terminals:

Connect the wiring from the sensors to these

terminals. Note the polarity:  (+) is a 13.5 VDC, 100 mA power
supply (to be connected to the red wire of a Flowline sensor), and
(-) is the return path from the sensor (to be connected to the black
wire of a Flowline sensor). (S) is the Relay signal input to be con-
nected to the white wire with the Green wire returning to the (-)
terminal.

3/4" NPT Mounting Thread:

Installation of the compact relay controller takes advantage of the
3/4" NPT thread located on its base. This makes the controller fully
compatible with any of Flowline's level switches or Smart Trak™ or
Switch Pak™ mounting systems.

Always tighten the controller
from the wrench flat located
on the swivel base. Never
tighten from the body of the
controller.

Switch Cable:

When installing a Flowline flow switch,
adjust the cable away from the printed cir-
cuit boards in the controller body. Avoid
breaking the seal between the top of the
level switch and the plastic coated cable.

Connecting switches to input terminals:

Please note a difference between FLOWLINE flow switches. All flow
switches (models FT10-___5 and GT10-___5) will be wired with the
Red wire to the (+) terminal, the Black wire to the (-) terminal and the
White wire to the (S) terminal.  See the illustration below to indicate
wiring for your switch. Note: the Shield wire will be used only for
long cable runs or where excessive electrical noise is present.

Flow Switch

Flow Switch

Normally Closed

Normally Open

INVERINVER

T

 +/- +/-

DELAY

AC

AC

GND

NC

C

NO

R

R

P

P

Input 1A

(S)

(-)

115 VAC
220 VAC

(+)

1

3

6

4

2

5

8

7

3"

1"

(S)

(-)

(+)

White

Black
Green

Models:

FT10-___5

GT10-___5

Red

(S)

(-)

(+)

White

Red
Green

Models:

FT10-___5

GT10-___5

Black

(S)

(-)

(+)

White

Black
Green

Models:

L_1_-___5

Red

(S)

(-)

(+)

White

Red
Green

Models:

L_1_-___5

Black

Level Switch

Level Switch

Normally Open

Normally Closed 

Содержание LC30-1001

Страница 1: ...ct has remained unclaimed at Flowline for longer than 30 days after dutifully requesting disposition of the product THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE OF THIS WARRANTY This warranty and the obligations and liabilities of Flowline under it are exclusive and instead of and the original purchaser hereby waives all other remedies warranties guarantees or liabilitie...

Страница 2: ...Certificate LR 79326 3 CE compliance EN 61326 EMC EN 61010 1 Safety Part Number Information Part Thread Description LC30 1001 1 2 3 4 NPT Flow or No Flow Relay Controller LC30 1051 1 2 3 4 BSP Flow or No Flow Controller LC30 1002 2 3 4 NPT Flow or No Flow Controller with Strobe Alert LC30 1052 2 3 4 BSP Flow or No Flow Controller with Strobe Alert 1 Adding CE to end of part number signify CE confi...

Страница 3: ... an inrush current charac teristic that may be 10 to 20 times their steady state load rating The use of a contact protection circuit may be necessary for your instal lation if the 10 amp rating does not provide an ample margin for such inrush currents Make a Fail Safe System Design a fail safe system that accommodates the possibility of relay or power failure If power is cut off to the controller ...

Страница 4: ...s Note the polarity is a 13 5 VDC 100 mA power supply to be connected to the red wire of a Flowline sensor and is the return path from the sensor to be connected to the black wire of a Flowline sensor S is the Relay signal input to be con nected to the white wire with the Green wire returning to the terminal 3 4 NPT Mounting Thread Installation of the compact relay controller takes advantage of th...

Страница 5: ...w flow condition could be lost The system must alert the operator not only to low flow but to controller power loss To do this connect the hot lead of the alarm to the NC side of the relay ter minal of the controller If power is lost the relay will be de energized and the alarm will sound if there is still power to the alarm circuit itself The alarm circuit should have a non interruptible power su...

Страница 6: ...e for your application follow the calibration steps listed below Note the switch s internal LED will be on when the switch detects no flow and will off when the switch detects flow 1 Install the fitting and flow switch as described in the Installation section of this manual Turn the flow switch and controller power on and adjust the flow rate to the application setting If the medi um to be sensed ...

Отзывы: