Step One

SPECIFICATIONS

Supply voltage:

120 / 240 VAC, 50 - 60 Hz.

Consumption:

5 watts

Strobe type:

10_1: N/A
10_2: Xenon tube

Strobe flash:

10_1: N/A
10_2: 1 per second

Sensor input:

(1) four-wire flow switch

Sensor supply:

13.5 VDC @ 100 mA

Contact type:

(1) SPDT

Contact rating:

250 VAC, 10A, 1/4 Hp

Contact delay:

0 to 60 seconds

LED indication:

Sensor, relay & power status

Electronics temp.:

F: -40° to 158°
C: -40° to 70°

Enclosure rating:

NEMA 4X (IP65)

Enclosure material:

10_1: PP (U.L. 94 VO)
10_2: PP (U.L. 94 VO) & polycarbonate

Encl. mount:

100_: 3/4” NPT
105_: 3/4” R

Enclosure rotation:

300° swivel base

Conduit entrance:

Single, 1/2" NPT

Classification:

general purpose

Certificate:

LR 79326-3

CE compliance:

EN 61326

EMC

EN 61010-1

Safety

Part Number Information:

Part #

Thread

Description

LC30-1001

(1) (2)

3/4” NPT

Flow or No-Flow Relay Controller

LC30-1051

(1) (2)

3/4” BSP

Flow or No-Flow Controller

LC30-1002

(2)

3/4” NPT

Flow or No-Flow Controller with Strobe Alert

LC30-1052

(2)

3/4” BSP

Flow or No-Flow Controller with Strobe Alert

(1)

Adding -CE to end of part number signify CE configuration of controller

(2)

Adding -E to end of part number signify 240 VAC configuration of controller

1.0"

(25mm)

4.7" 

(1

19mm)

2.8"

(71mm)

3.2" 

(81mm)

1.0"

(25mm)

2.8"

(71mm)

3.2" 

(81mm)

6.4" 

(162mm)

INVERINVER

T

 +/- +/-

DELAY

AC

AC

GND

NC

C

NO

R

R

P

P

Input 1A

(S)

(-)

115 VAC
220 VAC

(+)

Latch/Invert Logic

Time Delay

Sensor

Input

1

+       -       S  

NO

NC

COM

AC

AC

GND

RELAY

POWER

SUPPLY

Dimension:
LC30-10_1

Dimension:
LC30-10_2

Internal Controller Logic

LC11-1001 Faceplate

Содержание LC30-1001

Страница 1: ...ct has remained unclaimed at Flowline for longer than 30 days after dutifully requesting disposition of the product THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE OF THIS WARRANTY This warranty and the obligations and liabilities of Flowline under it are exclusive and instead of and the original purchaser hereby waives all other remedies warranties guarantees or liabilitie...

Страница 2: ...Certificate LR 79326 3 CE compliance EN 61326 EMC EN 61010 1 Safety Part Number Information Part Thread Description LC30 1001 1 2 3 4 NPT Flow or No Flow Relay Controller LC30 1051 1 2 3 4 BSP Flow or No Flow Controller LC30 1002 2 3 4 NPT Flow or No Flow Controller with Strobe Alert LC30 1052 2 3 4 BSP Flow or No Flow Controller with Strobe Alert 1 Adding CE to end of part number signify CE confi...

Страница 3: ... an inrush current charac teristic that may be 10 to 20 times their steady state load rating The use of a contact protection circuit may be necessary for your instal lation if the 10 amp rating does not provide an ample margin for such inrush currents Make a Fail Safe System Design a fail safe system that accommodates the possibility of relay or power failure If power is cut off to the controller ...

Страница 4: ...s Note the polarity is a 13 5 VDC 100 mA power supply to be connected to the red wire of a Flowline sensor and is the return path from the sensor to be connected to the black wire of a Flowline sensor S is the Relay signal input to be con nected to the white wire with the Green wire returning to the terminal 3 4 NPT Mounting Thread Installation of the compact relay controller takes advantage of th...

Страница 5: ...w flow condition could be lost The system must alert the operator not only to low flow but to controller power loss To do this connect the hot lead of the alarm to the NC side of the relay ter minal of the controller If power is lost the relay will be de energized and the alarm will sound if there is still power to the alarm circuit itself The alarm circuit should have a non interruptible power su...

Страница 6: ...e for your application follow the calibration steps listed below Note the switch s internal LED will be on when the switch detects no flow and will off when the switch detects flow 1 Install the fitting and flow switch as described in the Installation section of this manual Turn the flow switch and controller power on and adjust the flow rate to the application setting If the medi um to be sensed ...

Отзывы: