Installation
Warning - Flowline Ultrasonic transmitters have been optimized for use in non-metallic fittings.
For best performance, avoid the use of metallic fittings. Install the appropriate installation
fitting. Make sure that the fitting and transmitter threads are not damaged or worn. Install the
transmitter with the included Viton mounting gasket. Hand-tighten the transmitter within the
fitting. Perform an installed leak test under normal process conditions prior to system start up.
Do not install at
angle relative to the
liquid.
Do not install within
3” of tank sidewall.
Do not install with
objects in the beam.
Do not install in
applications with
vacuum.
Fitting Selection: Check the part number to determine the required fitting mount size and thread
type. EchoSwitch II is commonly installed in tank adapters, flanges, brackets or standpipes.
Note: Always include the gasket when installing the EchoSwitch II.
1.
Tank Adapter:
Select a tank adapter fitting with minimal height so as to ensure that the
installed transducer will not be substantially elevated into the fitting such as the Hayward
2” Tank Adapter (socket by thread). For the LU77-5005 version s, add a Reducer
Bushing such as the Spears 2” x 1”, thread x thread, Reducer Bushing (series 839-249,
Flowline p/n LM52-1001). Avoid tank adapter (thread x thread) styles and/or pipe stops
forward of the installed transducer.
2” Tank Adapter
Socket x Thread
Tank Adapter
w/ 2”x1” Reducer Bushing
Tank Adapter
Thread x Thread
Do not use thread x thread