MN300610 Rev C3
21
|
Appendix
Step Nine
FACTORY DEFAULT
Pressing the Factory Config button in the Configuration menu will return the screen to the following settings.
Out of the box, the EchoSonic
®
will output a 4-20 mA output that is maximized for its operational range. The
transmitter can be used in the original factory setting without configuration with WebCal
®
. Use the table below
to identify the configuration of the sensor out of the box.
Factory Default Table
Part
Number
Sensor
Height
Fill
Height
Loop
Fail-Safe
Output
at Empty
Startup
Condition
LU27-_ _
Series
300 cm
(118.1”)
290 cm
(114.1”)
Overfill
(22 mA)
4 mA @
Bottom
Empty
LU23-_ _
Series
550 cm
(216.5”)
530 cm
(208.7”)
Overfill
(22 mA)
4 mA @
Bottom
Empty
LU28-_ _
Series
800 cm
(315.0”)
780 cm
(307.1”)
Overfill
(22 mA)
4 mA @
Bottom
Empty
LU29-_ _
Series
1000 cm
(393.7”)
980 cm
(385.8”)
Overfill
(22 mA)
4 mA @
Bottom
Empty