MN310125 Rev A2
9
|
Getting Started
(continued)
Step Two
BASIC CONFIGURATION
EchoPod
®
can be configured using the Flowline
™
on-line free WebCal
®
software download coupled to a USB
®
port with a USB
®
Fob.
EchoPod
®
can be configured before installation or after installation. The transmitter features non-volatile
memory, so any settings configured before installation will not be lost when the sensor is powered down To
start, the following information is required:
Basic Tank Information
o
HEIGHT
(Sensor Height) – Distance from
the bottom of the tank to the bottom of the
sensor.
o
FILL-H
(Fill-Height) – Distance from the
bottom of the tank to the fill-height of the
liquid.
Power:
o
Provide input power to the EchoPod
®
Note:
The
HEIGHT
and Fill-Height (
FILL-H
) settings also determine the 4 to 20 mA current span. The
HEIGHT
setting determines the 4mA position and the
FILL-H
setting determines the 20 mA position.
BASIC RELAY SETTINGS
High Alarms
(Hi)
– Used to energize a relay
(ON) when the level reaches the Hi setting.
Relay will de-energize (OFF) when level falls
below the original setting.
Tank Fill
(ON & OFF)
– Used to automatically
fill a tank using only one relay. Relay
energize at ON level and remains energized
until it reaches the OFF level where it de-
energizes. Relay remains de-energized until
the level falls below ON level.
Tank Empty (not shown)
– is the exact
opposite of Tank Fill. One relay is used to
empty the tank with ON set to a high point in
the tank and OFF set to a low point.
Lo Alarm
s (Lo)
– Used to energize a relay (ON) when the level falls below the Lo setting. Relay will
de-energize (OFF) when level rises above the original setting.
Note:
All relay settings are referenced from the Empty or 4mA setting of the tank.