QS302100 Rev. A
3
|
INSTALLING THE LOOP-POWERED METER
When unpacking the Loop-Powered Meter, thoroughly inspect the unit for any damage that may have occurred
during shipping. Be sure to report any damage, as well as any missing parts or malfunctions to your supplier or
Flowline.
MOUNTING THE PANEL
When mounting the panel, first prepare a standard 1/8
DIN panel cutout – 3.622" x 1.772" (92 mm x 45 mm),
as shown in the following diagram.
Allow at least 4.0" (102 mm) clearance behind the
panel for wiring.
Be sure to maintain a minimum panel thickness of
0.04" - 0.25" (1.0 mm - 6.4 mm) to maintain type 4X
rating. This would equal 0.06" (1.5 mm) for a steel
panel and 0.16" (4.1 mm) for a plastic panel.
Remove the Loop-Powered Meter’s two mounting
brackets. Back-off the two screws so that there is ¼"
(6.4 mm) or less through the bracket. Slide the
bracket toward the front of the case and remove it.
Insert the Loop-Powered Meter into the panel cutout.
Install the mounting brackets and tighten the screws
against the panel. To achieve a proper seal, tighten
the mounting bracket screws evenly until Loop-
Powered Meter fits snug against the panel along its
short side. DO NOT OVER TIGHTEN or the rear of
the panel may be damaged.