Commander LI90 Series
Rev 1_3
•
Configuration of Outputs
o
Once in the Secured Function Section, press the Config Outputs soft key
o
Each relay will ask for a Relay ON and Relay OFF level. These settings must be
in the same units used for the Empty and Full settings
Relay ON
Relay OFF
•
If you are reading between 0 to 500 gallons, then the relay set points must
be in gallons
•
For Pumps and Valves, use both settings as the ON/OPEN and
OFF/CLOSE points for the device
•
For Alarms, use the ON point where the relay will start and the OFF as a
hysteresis to prevent chattering of the relay
High Alarm
Low Alarm
Automatic Fill
Automatic Empty