Information
Current flow rate
1
.
Indicates current flow rate in
l/sec, l/hr or GPM.
Display
Description
Values
Indicates unit scale system.
l/sec or l/min or GPM.
mA or VDC.
Indicates battery level.
Basic version with no battery (SM.0.0.0.3)
Failsafe version with battery (SM.0.0.0.4)
Battery level low, charging needed.
Medium battery level.
Battery charged.
Alarm indicator.
Blinking if actuator is still functional (warning).
Fully on if actuator is not working (critical).
CONTROL SIGNAL 2.0 VDC
FEEDBAC SIGNAL 2.0 VDC
VALVE SM. 3.1
pressur range 30-800 kpad
MAXIMUM FLOW RATE 6.580 L/SEC
OPERAT DIRECT NC
FAIL SAFE DIRECT CLOSE
ERROR CODE 01
Information
Control signal
Indicates value of control signal.
2-10V DC
Feedback signal
Indicates value of feedback signal.
2-10V DC
Valve
Indicates valve model.
From SM.3.0 and up...
Pressure range
Indicates pressure range.
30-600 kPaD, 35-600 kPaD or 50-600 kPaD /
4.5-87 psid, 5.1-87 psid or 7.3-87 psid.
Maximum flow rate
Indicates selected maximum de-
signed flow rate.
Depends on valve etc.
l/sec, l/hr or GPM
Operational direction
Indicates direction of rotation.
NC
Failsafe direction
Indicates failsafe direction.
Open or Closed
Valid for failsafe actuator models
Critical Alarm
Indicates alarm error code.
01, 03, 05 (without failsafe) or 06.
Only if critical alarm is present.
In Operation
Note 1: The flow rate shown on the actuator display is a calculated value. Flow rates below 1.0 valve rotation is shown as indications,
illustrated with an apostrophe in front of the flow rate. If display shows “NA” the valve model has not been chosen in programming menu step 2.
Use
to go to next information line and
to go
to the previous.