Auto-stroke sequence
In case the valve does not operate as expected,
start the auto-stroke sequence to re-calibrate
the closing point making sure that the actuator
is able to open the valve fully. Press
and
simultaneously for 6 seconds to start auto-stroke.
An auto-stroke sequence cannot be cancelled.
During auto-stroke actuator display will show
“
AUTO STROKE CYCLES
”
. Hereafter it will proceed to
normal operation mode (according to control sig-
nal). If the actuator is not able to open valve fully,
error code 01 will be displayed.
Manual Override
Manual override is used to temporarily set the
valve position regardless the settings and con-
trol signal for the actuator. Disconnect power to
the actuator and remove the actuator from the
valve. Turn the valve spindle clockwise to close
valve and counter-clockwise to open. Re-mount
the actuator and connect power. Be aware to
protect that actuator from water while not on the
valve.
When manually operating the vale (actua-
tor disconnected) do not use more than 10
Nm torque. Use of higher torque will void
warranty.
Failsafe Mode
In case of power failure, failsafe models will
move actuator to the position chosen in pro-
gramming menu step 13 and show warning code
05 in the actuator display. When voltage is back
in range
⚠
will be reset.
This paper is a supplement to the
FlowCon General Instruction
Latest release of any FlowCon material is available on
FlowCon FIT 65-250 mm (2 1/2”-10”)
1B95095 - 02/2020
Page 10 of 10
FlowCon International assumes no responsibility for mistakes, if any
, in any printed material.