FlowCon FN.0.2 Скачать руководство пользователя страница 4

FN.0.2

FN.0.4

FN.1.2

Normal operation mode

Full on green

Full on green

Full on green

Charging mode (60 sec)

n/a

n/a

Blinking red

Calibration mode

(closing point adjustment)

Blinking green

Blinking green

Blinking green

Electrical override mode

Blinking red/green Blinking red/green Blinking red/green

Failsafe mode

n/a

n/a

OFF

LED Status

The LED indicator is visible through the dark colored transparent connection cover. The LED indica-

tion will give the following statuses.

This paper is a supplement to the

 FlowCon General Instruction 

Latest release of any FlowCon material is available on

 

www.flowcon.com

FlowCon FN.0.2, FN.0.4 and FN.1.2 Actuators

1B95080 - 08/2019-2

Page 4 of 4

FlowCon International assumes no responsibility for mistakes, if any

, in any printed material.

Содержание FN.0.2

Страница 1: ...nt the actuator on the valve and finger tighten the connection union Do not use addi tional tools In case the actuator will have to be removed it is recommended to electrically open the actuator by activating DIP switch 6 for eas ier removal Hereafter finger loosen the connec tion union Again no need for additional tools Please make sure that the actuator is electrically opened before re fitting i...

Страница 2: ...ed during commission ing It prevents the valve from jamming when the valve is not moved for a longer period of inactiv ity By moving DIP switch 1 from OFF to ON Auto Cycle is activated Actuator will then per form 50 stroke cycle every 3 weeks if no stroke movement has occurred Electrical Override By moving DIP switch 6 from OFF to ON elec trical override is activated and the actuator will open val...

Страница 3: ...ectrical override ON Electrical override OFF 5 Failsafe open Failsafe close 4 Equal percentage Linear 3 Normally Open Normally Closed 2 Control signal 2 10V Control signal 0 10V 1 Auto cycle ON Auto cycle OFF 6 5 4 3 2 1 DIP Switch Settings The valve functions are set on DIP switches found under the connection cover PCB mounted electri cal components will not be directly exposed when DIP switches ...

Страница 4: ...ing red green Failsafe mode n a n a OFF LED Status The LED indicator is visible through the dark colored transparent connection cover The LED indica tion will give the following statuses This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www flowcon com FlowCon FN 0 2 FN 0 4 and FN 1 2 Actuators 1B95080 08 2019 2 Page 4 of 4 FlowCon...

Отзывы: