FlowCon FN.0.2 Скачать руководство пользователя страница 3

DIP 

switch

Function ON

Function OFF

#6

Electrical override ON

Electrical override OFF

#5

No function

No function

#4

Equal percentage

Linear

#3

Normally Open

Normally Closed

#2

Control signal 2-10V

Control signal 0-10V

#1

Auto cycle ON

Auto cycle OFF

6
5
4
3
2
1

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

DIP 

switch

Function ON

Function OFF

#6

Electrical override ON

Electrical override OFF

#5

No function

No function

#4

No function

No function

#3

Normally Open

Normally Closed

#2

No function

No function

#1

No function

No function

6
5
4
3
2
1

%

%

%

%

%

%

%

%

DIP 

switch

Function ON

Function OFF

#6

Electrical override ON

Electrical override OFF

#5

Failsafe open

Failsafe close

#4

Equal percentage

Linear

#3

Normally Open

Normally Closed

#2

Control signal 2-10V

Control signal 0-10V

#1

Auto cycle ON

Auto cycle OFF

6
5
4
3
2
1

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

%

DIP Switch Settings

The valve functions are set on DIP switches found under the connection cover. PCB mounted electri-

cal components will not be directly exposed when DIP switches are to be set. Factory setting for all 

switches is OFF.

 

FlowCon FN.0.2 Actuator

FlowCon FN.0.4 Actuator

 

FlowCon FN.1.2 Actuator

FlowCon FN.0.2, FN.0.4 and FN.1.2 Actuators

1B95080 - 08/2019-2

This paper is a supplement to the

 FlowCon General Instruction 

Latest release of any FlowCon material is available on

 

www.flowcon.com

Page 3 of 4

Содержание FN.0.2

Страница 1: ...nt the actuator on the valve and finger tighten the connection union Do not use addi tional tools In case the actuator will have to be removed it is recommended to electrically open the actuator by activating DIP switch 6 for eas ier removal Hereafter finger loosen the connec tion union Again no need for additional tools Please make sure that the actuator is electrically opened before re fitting i...

Страница 2: ...ed during commission ing It prevents the valve from jamming when the valve is not moved for a longer period of inactiv ity By moving DIP switch 1 from OFF to ON Auto Cycle is activated Actuator will then per form 50 stroke cycle every 3 weeks if no stroke movement has occurred Electrical Override By moving DIP switch 6 from OFF to ON elec trical override is activated and the actuator will open val...

Страница 3: ...ectrical override ON Electrical override OFF 5 Failsafe open Failsafe close 4 Equal percentage Linear 3 Normally Open Normally Closed 2 Control signal 2 10V Control signal 0 10V 1 Auto cycle ON Auto cycle OFF 6 5 4 3 2 1 DIP Switch Settings The valve functions are set on DIP switches found under the connection cover PCB mounted electri cal components will not be directly exposed when DIP switches ...

Страница 4: ...ing red green Failsafe mode n a n a OFF LED Status The LED indicator is visible through the dark colored transparent connection cover The LED indica tion will give the following statuses This paper is a supplement to the FlowCon General Instruction Latest release of any FlowCon material is available on www flowcon com FlowCon FN 0 2 FN 0 4 and FN 1 2 Actuators 1B95080 08 2019 2 Page 4 of 4 FlowCon...

Отзывы: