![FlowCon ABM Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/flowcon/abm/abm_installation-and-operation-instruction-manual_2308016002.webp)
DYNAMIC BALANCED
TEMPERATURE CONTROL VALVE
FlowCon ABM
1M95000ISO
-
04/2016
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.
Denmark
Dubai
USA
Singapore
- 2 -
Figure 2
Figure 3
Actuators
The ABM valve should be installed so that the
actuator is located upwards and higher above
the valve center-line to prevent condensation
into the electronics. Valves are supplied in open
position.
Mechanical installation
1) Depress the clutch and manually close the
damper blades and position the actuator at 0°
or 90° so that the damper and the actuator co-
incide. NOTE: do not clutch the actuator when
the power is on.
2) Slide the actuator onto the shaft.
3) Tighten the nuts on the “U”-bolt to the shaft
with an 8mm wrench to a torque of 6.7Nm.
4) Slide the mounting bracket under the actua-
tor. Ensure free movement of the slot at the
base of the actuator. The bracket pin must be
placed in the mid distance of the slot.
Manual over-ride operation
1) DISCONNECT POWER. Failure to discon-
nect power may cause damage to the actua-
tor gears.
2) Fit the manual over-ride key onto the valve
spindle.
3) Press the clutch.
4) Rotate the manual over-ride key to open or
close the valve as required. CW will close the
valve and CCW will open the valve.
Actuator wiring
1) Remove the actuator cover by loosening the
cover screw.
2) Connect the wiring, pls. see figures 4-6.
Screw-terminals 6, 7 and 8 are only used on
actuators with end switches.
3) SW1 controls the direction of the rotation,
please see figures 4-6 for clock-wise (0 to 90°)
and counter-clock-wise (90 to 0°) rotation.
4) For actuators with end switches, the mechani-
cal auxiliary switches are fixed at 10° and 80°.