5.4.9. AF CONTROL SYSTEM
– MASTER-SLAVE CONNECTING
To connect air curtains among them selves and controlling them by single controller is possible to use MASTER/SLAVE mode.
Execute listed steps:
1)
Turn off the unit
;
2) Set S2 and S3 dip switches (regards both: Master and Slave unit) as shown:
Dip switch
S2
1
2
3
4
Dip switch
S3
1
2
3
4
switch down position
switch up position
3) Set dip switches S1 and S4 in Master air curtain as shown:
Dip switch
S1
1
2
3
4
Dip switch
S4
1
2
3
4
Set dip switches S1 and S4 in Slave air curtain as shown:
Dip switch
S1
1
2
3
4
Dip switch
S4
1
2
3
4
4) Turn on power supply (30 sec) - green leds indicate saved configuration;
5) Turn off power supply;
6) Set S2 and S3 dip switches (regards both: Master and Slave unit) as shown:
Przełącznik
S2
1
2
3
4
Przełącznik
S3
1
2
3
4
7) Use cable with R11 plugs or OMY 2x0,5mm2 cable to chain air curtains and share control signals between Master and
Slave (Slaves) unit. Each curtain must be supplied with current separately.
connecting diagram:
8) Turn on power supply - unit is ready to operate mode choose, set it on dip switch S3 (and additional settings S1, S2, S4)
for each Elis unit. Each air curtain must have the same configuration of those dip switches.