ELiS AX air curtain is a high-quality device that, by creating an air barrier, reduces heat losses. The device is dedicated ONLY for indoor use.
The ELiS AX air curtain is intended for horizontal installation above a door opening or vertical installation with a door opening with a
maximum height of 4,5 m.
The air curtain is available in a version with a water 3-row or 4-row heat exchanger:
•
ELiS AX36-W3R-100, ELiS AX36-W3R-150, ELiS AX36-W3R-200, ELiS AX36-W3R-250 – air curtains with 3-row water heat exchanger
with a maximum range of 3,6 m*,
•
ELiS AX36-W4R-100, ELiS AX36-W4R-150, ELiS AX36-W4R-200, ELiS AX36-W4R-250 – air curtains with 4-row water heat exchanger
with a maximum range of 3,6 m*,
•
ELiS AX45-W3R-100, ELiS AX45-W3R-150, ELiS AX45-W3R-200, ELiS AX45-W3R-250 – air curtains with 3-row water heat exchanger
with a maximum range of 4,5 m*,
•
ELiS AX45-W4R-100, ELiS AX45-W4R-150, ELiS AX45-W4R-200, ELiS AX45-W4R-250 – air curtains with 4-row water heat exchanger
with a maximum range of 4,5 m*.
* according to ISO 27327-1
❶
ADVICE
1.
The use of an air curtain is recommended for public buildings .
2.
Underpressure in the building significantly reduces the efficiency of the air barrier, the ventilation system should be
balanced.
3.
At a wind speed of more than 3 m/s, the heated version of air curtain should be used to increase user comfort.
3.
TECHNICAL DATA ELIS AX
ELiS AX36-
W3R-100
ELiS AX36-
W3R-150
ELiS AX36-
W3R-200
ELiS AX36-
W3R-250
ELiS AX36-
W4R-100
ELiS AX36-
W4R-150
ELiS AX36-
W4R-200
ELiS AX36-
W4R-250
Power supply [V/Hz]
230/50
230/50
230/50
230/50
230/50
230/50
230/50
230/50
Max. current consumption [A]
2,3
3,3
5,6
6,4
2,2
3,2
5,5
6,3
Power consumption [kW]
0,27
0,40
0,67
0,81
0,27
0,40
0,67
0,81
IP
21
Connection stub ['']
3/4
Air volume
(1)
[m
3
/h]
900 - 1800
1200-2700
2000-4300 2300-5300
800-1700
1100-2600
1900-4200 2200-5200
Acoustic pressure level
(2)
[dB(A)]
42-60
43-61
45-63
46-64
41-59
42-60
44-62
45-63
Acoustic power level
(3)
[dB(A)]
58-76
59-77
61-79
62-80
57-75
58-76
60-78
61-79
Heating power
(4)
[kW]
8,1-12,9
11,8-20,5
17,1-29,0
21,4-38,0
8,7-15,2
12,7-24,1
20,6-36,7
24,7-46,6
Temperature increase
(4)
(ΔT ) [°C]
26-21
29-22
25-20
27-21
32-26
34-27
31-26
33-26
Max. Water pressure [MPa]
1,6
Max. water temperature [˚C]
60
Device mass [kg]
38,5
53,3
71,7
86,8
40,0
55,6
74,8
90,3
Range
(1)
[m]
3,6
4,
5 m
3,
6
m
PIC. 2.1 ELIS AX45 RANGE.
PIC. 2.2 ELIS AX36 RANGE.
PIC. 2.3 DIRECTION OF AIR FLOW.
❶
INLET
❷
OUTLET