9.  FILTERS REPLACEMENT  

Elis  curtains  can  be  equipped  with  EU2  filters.  Filters  need  to 
be  replaced  periodically.  Filled  filters  can  causes  in  Air  flow 
drop.  

Replacing of filters step by step: 

1.  Dismount inlet grill guard (unscrew the screws). 

 
 

 
 
 
 
 

2.  Dismount filters holders by unscrewing screws 

 

 

 

 
 

 

3.  Install grill guard

 

 
 

10.  CLEANING AND CONSERVATION 

Periodically  need  to  be  checked  exchanger  condition. 
Exchanger  filled  with  dirt  causes  in  heat  output  and  air  flow 
drop.  
If cleaning of heat exchanger is needed use listed  guidelines.  

  Disconnect power supply of unit. 

 

  Dismount inlet grill guard

 

  It  is  recommended  to  use  pressured  air  to  clean  the 

exchanger, air stream need to be directed perpendicular to 
exchanger and moved along lamellas.

 

  It  is  prohibited  to  use  water  or  sharp  items  to  clean 

exchanger.

 

 

  Other installed equipment do not need be cleaned. 

 
 
 
 
 
 
 
 
 

11. SERVICE 

In the case of any irregularities in the device operation, please 
contact the manufacturer’s service department. 

The  manufacturer  bears  no  responsibility  for  operating  the 
device  in  a  manner  inconsistent  with  its  purpose,  by  persons 
not authorized for this, and for damage resulting from this! 

Made in Poland 

Made in EU 

Ma

nufacturer: FLOWAIR GŁOGOWSKI I BRZEZIŃSKI SP.J. 

ul. Chwaszczyńska 151E, 81-571 Gdynia 

phone. +48 58 669 82 20, fax.: +48 58 627 57 21 

e-mail: 

[email protected]

 

www.flowair.com 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Содержание ELIS A-E-100

Страница 1: ...TECHNICAL DOCUMENTATION OPERATION MANUAL DTR ELIS A 4 0 2015 10 22 PL ...

Страница 2: ...in the operation manual at any time and without notice and also to make changes in the device without influencing its operation This manual is an integral part of the device and it must be delivered to the user together with the device In order to ensure correct operation of the equipment get thoroughly acquainted with this manual and keep it for the future The devices may only be installed and op...

Страница 3: ...HNICAL DATA A W 100 A N 100 A E 100 A W 150 A N 150 A E 150 A W 200 A N 200 A E 200 Power supply V Hz 230 50 3x400 50 230 50 3x400 50 230 50 3x400 50 Power consumption kW 0 17 7 0 25 10 7 0 34 15 Current consumption A 0 72 10 1 1 15 5 1 45 21 5 IP Insulation class 21 F Connecting stub Max water temperature o C 95 95 95 Max water pressure MPa 1 6 1 6 1 6 1 6 Temperature increase T ºC 34 25 25 21 24...

Страница 4: ...0 A N 200 A E 200 3 50dB A 53dB A 55dB A 2 43dB A 46dB A 48dB A 1 39dB A 42dB A 44dB A Acoustic pressure level measured in the room of average sound absorption capacity 500m3 at the distance of 3 m apart of the unit 2 4 AIR VOLUME step A W 100 A N 100 A E 100 A W 150 A N 150 A E 150 A W 200 A N 200 A E 200 3 1500m 3 h 2500 m 3 h 3500 m 3 h 2 1150m 3 h 2100 m 3 h 2900 m 3 h 1 800m 3 h 1650 m 3 h 24...

Страница 5: ... 9 218 268 319 0 7 1 0 1 4 30 28 26 10 8 3 10 1 12 0 361 443 526 1 7 2 4 3 3 38 35 33 6 4 7 9 9 4 186 230 274 0 5 0 8 1 1 31 30 28 15 7 2 8 9 10 5 316 388 461 1 3 1 9 2 6 40 37 35 5 2 6 6 7 9 153 191 229 0 4 0 6 0 8 33 32 30 20 6 2 7 6 9 1 271 334 397 1 0 1 5 2 0 42 40 38 3 9 5 1 6 3 114 150 182 0 2 0 4 0 5 34 33 32 Tw1 Tw2 60 40 o C Tw1 Tw2 50 40 o C 0 850 1150 1500 8 3 10 1 12 0 360 442 525 1 8 ...

Страница 6: ...A W 200 PT Qw Δpw Tp2 PT Qw Δpw Tp2 Tp1 V kW l h kPa C kW l h kPa C C m 3 h Tw1 Tw2 90 70 o C Tw1 Tw2 80 60 o C 0 2400 2900 3500 25 7 29 32 2 1135 1271 1419 12 14 5 18 32 29 27 22 24 7 27 6 970 1086 1212 9 11 1 13 6 27 25 23 5 24 27 30 1063 1191 1329 10 4 13 16 35 32 30 20 4 22 9 25 5 898 1006 1122 7 8 9 7 11 8 30 28 27 10 22 5 25 1 28 992 1110 1240 9 2 11 3 14 38 36 34 18 8 21 23 5 825 924 1031 6...

Страница 7: ...e by side While mounting ELiS A side by side it is important to start from right side like is shown below all electrical conntection should be done before installing following curtain 4 1 RECOMMENDATION OF MONTAGE DISTANCES 4 2 MOUNTING BY RODS UNDER THE CEILING While mounting curtains under the ceiling 4 rods M8 should be screwed minimum 20 mm deep ...

Страница 8: ...LS BY THE BRACKETS ELIS A W 100 A N 100 A E 100 A W 150 A N 150 A E 150 A W 200 A N 200 A E 200 4 4 BRACKETS Brackets ELiS A 2 x bracket ELiS A 4 x plug Ø10 4 x double threaded screw M8 4 x washer M8 4 x nut M8 4 x allen screw M8 not included ...

Страница 9: ...r com 9 4 5 STAGES OF INSTALATION Curtain Type Distance between brackets mm ELiS A W 100 ELiS A E 100 ELiS A N 100 970 ELiS A W 150 ELiS A E 150 ELiS A N 150 1440 ELiS A W 200 ELiS A E 200 ELiS A N 200 1895 1 2 3 ...

Страница 10: ...m mechanical door contact Operating temperature range 10 80 o C IP Insulation class IP 65 Connectors 1xNC i 1xNO Max current resistive 10A inductive 3A Max Power load 300Vac or 250Vdc DCe magnetic door contact Operating temperature range 5 60 o C IP Insulation class IP 64 Connectors NC Max current inductive resistive 0 5A Max power Load 175Vdc Lenght of cabel 2m Max operating contactors distance 8...

Страница 11: ...ed operating S1 S2 S3 signalize number of set fan speed T signalize of valve set DC signalize of door contact set OPEN CLOSE signalize valve actuator WORK signalize of software working SW3 operating mode switch default settings 1 Device function selection BMS Address adjustment 2 MASTER mode operating SLAVE mode operating 3 Curtain Heater DUO 4 ELiS W N ELiS E 5 K1 Programme K2 Programme 6 Operati...

Страница 12: ...y B Return pipe water supply 5 3 2 REGULATION TS ELIS A E WIRING DIAGRAMS Power supply 3x400V 50Hz ELiS A E 100 min 5x4 mm2 Overcurrent B16 ELiS A E 150 min 5x6 mm2 Overcurrent B20 ELiS A E 200 min 5x6 mm2 Overcurrent B25 Air curtain step switch with thermostat TS OMY 5x0 5mm 2 HEAT heating mode FAN room thermostat deactivated COOL cooling mode Door contact DCe DCm door closed contacts opened door...

Страница 13: ...y B Return pipe water supply 5 3 4 REGULATION T box ELIS A E WIRING DIAGRAMS Power supply 3x400V 50Hz ELiS A E 100 min 5x4 mm2 Overcurrent B16 ELiS A E 150 min 5x6 mm2 Overcurrent B20 ELiS A E 200 min 5x6 mm2 Overcurrent B25 T box OMY 4x0 5mm 2 Door contact DCe DCm door closed contacts opened door opened contacts closed ATTENTION Switch 4 on SW3 to the position E and then restart the system switch...

Страница 14: ...LAVE curtain 5 3 6 CONTROL SYSTEM BMS CONNECTION DRV driver has a possibility to be connected to integrated Building Management System BMS Parameters Name Description Physical layer RS485 Protocol MODBUS RTU Baud rate 38400 bps Parity Even Data bits 8 STOP bits 1 Connection must be made using 3 poliges wire to connectors IN A IN B GND SIGNAL GROUND UWAGA Dla ostatniego urządzenia pracującego w sie...

Страница 15: ...ermostat is off 1 HEAT_ON Curtain s thermostat is on 5 0x08 ContactDoor 0 1 Set value for door contact 0 DOOR_CLOSE Door is closed 1 DOOR_OPEN Door is opend Inputs Register Data write Lp Adres rejestru Nazwa parametru Min Max Opis 1 0x04 CurtainFanSpeed 0 3 Curent fan step 0 FAN_SPEED0 Fan is off 1 FAN_SPEED1 1st step of fan is on 2 FAN_SPEED2 2nd step of fan is on 3 FAN_SPEED3 3rd step of fan is ...

Страница 16: ... should be executed so that in the case of a failure it is possible to disassemble the device For this purpose it is best to use shut off valves just by the device The system with the heating medium must be protected against an increase of the heating medium pressure above the permissible value 1 6 MPa While screwing exchanger to pipeline connecting stubs has to be hold by wrench 8 OPERATION The d...

Страница 17: ...ount inlet grill guard It is recommended to use pressured air to clean the exchanger air stream need to be directed perpendicular to exchanger and moved along lamellas It is prohibited to use water or sharp items to clean exchanger Other installed equipment do not need be cleaned 11 SERVICE In the case of any irregularities in the device operation please contact the manufacturer s service departme...

Страница 18: ...tu product launch date 2014 jest zgodna z zasadniczymi wymaganiami was produced in accordance to the following European Directives dyrektywy directives MD 2006 42 WE dyrektywy directives EMC 2004 108 WE oraz zharmonizowanymi z tymi dyrektywami normami and harmonized norms with above directives PN EN 60204 1 2010 Bezpieczeństwo maszyn Wyposażenie elektryczne maszyn Część 1 Wymagania ogólne Safety o...

Страница 19: ...h mieszkalnym handlowym i lekko uprzemysłowionym Electromagnetic compatibility EMC Part 6 1 Generic standards Immunity for residential commercial and light industrial environments PN EN 61000 6 2 2008 Kompatybilność elektromagnetyczna EMC Część 6 2 Normy ogólne Odporność w środowiskach przemysłowych Electromagnetic compatibility EMC Part 6 2 Generic standards Immunity for industrial environments P...

Отзывы: